Plan Review Notes
Plan Review Notes For Permit 05061669
Permit Number 05061669
Review Stop E
Sequence Number 4
Notes
Date Text
2007-02-11 14:48:09*** UNSAT 4TH REVIEW***
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEWS WHICH STILL
 NEED TO BE ADDRESSED ALONG WITH NEW NOTES AS STATED
 BELOW.
  
  
 1) NOTE: PLEASE BE SURE PLANS CONTAIN ALL THE RELEVANT
 CODES AND YEARS IN WHICH THE PLANS ARE DESIGNED UNDER.
  
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY
 OTHER TRADE.
 ** THIS IS UNDER THE 2001 FBC \
 THE FOLLOWING MINIMUM CODES SHALL BE SHOWN ON PLANS
 WHICH ARE RELEVANT TO THE DESIGN OF PROJECT.
 2001 FBC, 2002 NFPA-70(NEC), 2003 NFPA-101, 2002
 NFPA-72 (WHERE APPLICABLE).
  
 2 ) NOTE: PLEASE SHOW AND COMPLETE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULE.
 THIS WAS STILL NOT DONE; THERE ARE SEVERAL ITEMS ON
 PLANS WHICH DO NOT CONTAIN CIRCUITS. PLEASE ALSO SEE
 CIRCUIT(S) ON PLANS WHICH DO NOT GO TO ANYTHING? PLEASE
 SEE THAT THE PANEL SCHEDULE SHALL BE SPECIFIC TO ALL
 CIRCUITS AND AREAS WHICH THEY FEED. PLEASE BE SURE THE
 CIRCUITS ON SCHEDULE CORRELATES TO THE PLANS FOR ANY
 ROOM AND AREA DESIGNATIONS. THIS REQUIRES THAT THE
 IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.
 FBC104.3.1.1 ADMIN SECT 2001.
 NEC 408.4, 240.4, 310.16
  
 3) NOTE: PLEASE SEE 700.12E AS THE EM AND EXT LTS SHALL
 BE CIRCUITED TO THE BRANCH CIRCUIT LIGHTING IN ANY ONE
 AREA WHERE THESE FIXTURES ARE LOCATED.
 PLEASE ALSO SEE COMMENT WITH RESPECT TO FIXTURES AND
 TYPES.
 THIS COMMENT WAS MADE ON PREVIOUS REVIEW FOR
 CIRCUITING.
  
 4) NOTE: PLEASE SHOW LOAD CALCULATIONS, WHICH ARE IN
 COMPLIANCE WITH THE 2002 NEC SECTION. 220.
 THIS WAS NOT DONE; THE CALCULATIONS SUBMITTED ARE NOT
 CODE COMPLIANT IN ANY FASHION.
 PLEASE INDICATE HOW LOADS WERE DERIVED ON A LOAD
 SUMMARY BASED FROM THE NEC. 220.
 220.3,220.10,220.11,220.12 220.13, ALL CONTINUOUS LOADS
 125% PER 215.3, 230.42 AND LARGEST MOTOR LOAD. PLEASE
 INCLUDE ALL EXISTING LOADS WITH NEW LOADS BEING ADDED.
 WHERE IS THE REST OF THE SERVICE FOR BUILDING WHICH
 THIS TENANT IS BEING ADDED TO EXISTING???
  
 5) NOTE: PLEASE CLARIFY MEANS OF EGRESS LIGHTING
 REQUIRED FOR REAR OF BLDG TO THE PUBLIC RIGHT OF WAY.
 THIS INCLUDES A BACK UP FIXTURE OF SOME TYPE. A NOTE ON
 PLANS WHICH MENTIONS LIGHTING TO BE INSTALLED DOES NOT
 COMPLY WITH SHOWING THE MINIMUM AS REQUIRED IN DESIGN.
 LS 101 2003, 7.8.1.3, 7.9.2.2. PLEASE KNOW, A MIN OF
 10FT CANDLES IS REQUIRED UNDER NORMAL AND 1FT CANDLE
 UNDER EM CONDITIONS. PLEASE SHOW.
  
 6) NOTE: PLEASE SEE NEW RISER SUBMITTED WHICH IS NOT
 CODE COMPLIANT.
 PLEASE SEE THE SERVICE ENTRANCE CONDUCTOR SIZES ALONG
 WITH FEEDERS ARE NOT OF SUFFICIENT SIZE TO CONFORM TO
 NEC 310.16.
 PLEASE SEE SOME OF THE CONDUCTOR SIZES AS SHOWN ARE NOT
 A STANDARD CONDUCTOR SIZE FROM THE STANDARDS OF AWG
 (AMERICAN WIRE GAUGE) OR NEC 310.16.
 PLEASE SEE SOME OF THE CONDUCTORS ARE ONLY RATED FOR
 200AMPS.
 PLEASE SEE NOTE WHICH MENTIONS *TO PANEL POLE* ? WHAT
 IS THIS?
 PLEASE COMPLETE CONDUCTORS IN GUTTER AND THE REST OF
 THE SERVICE. PLEASE SHOW ON PLANS.
 PLEASE INDICATE SIZE OF METER CAN/SERVICE BEING
 PROVIDED. PLEASE SEE NOTE #4 ABOVE.
  
 ? PLEASE SEE 240.4, 230.2, 110.26, 240.24, 408.7,
 215.5, 230.70, 240.6, ETC.
 ? THERE ARE TOO MANY SECTIONS TO LIST.
  
  
 7) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTOR AFTER THE FIRST MEANS OF DISCONNECT. AS THE
 SERVICE SHOWN IS NOT CLEAR FOR THE REST OF THE SERVICE,
 IT IS UNCLEAR WHAT AND WHERE EQUIPMENT GROUNDS ARE FOR
 THE SERVICE AND HOW THEY ARE TO BE INSTALLED AS NOT
 OTHER EQUIPMENT IS BEING SHOWN FOR THE SERVICE. PLEASE
 SEE 250.66, 250.6, 250.24B, 250.110, 250.50, 250.104
 AS THE GROUNDING ELECTRODE SYSTEM IS NOT COMPLETE AT
 THIS TIME.
  
 8) NOTE: PLEASE PROVIDE AND A SYMBOL/FIXTURE LEGEND.
 UNABLE TO REVIEW FIXTURES FOR EM / EXT, ARE THESE COMBO
 UNITS??
  
 8) NOTE: PLEASE SHOW LOCATION OF THE EXISTING SERVICE.
 PLEASE ALSO SHOW AND INDICATE THE LOAD ON THE EXISTING
 SERVICE WITH NEW LOAD ADDED. AS NOTED ABOVE IN NOTE #4
 AND NOTE #6.
 220 NEC
 FBC ADMIN SECT 104.3.1.1
  
 9) NOTE: PLEASE SEE 424.3B FOR MIN OCP FOR AHU. PLEASE
 SEE NO MECH PLANS SUBMITTED, UNABLE TO VERIFY THE KW
 RATING OF THE HEAT. PLEASE VERIFY AS THE 6.5 AS SHOWN
 DOES NOT SEEM TO BE A TYPICAL SIZE?
 PLEASE SEE THIS IS THE SAME COMMENT FROM PREVIOUS
 REVIEW.
  
 10) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE KNOW IF ANY
 OF THE NOTES ABOVE ARE NOTED ON THE FOLLOWING REVIEW
 FOR COMPLIANCE WHICH HAS NOT BEEN MADE, A FEE FOR PLAN
 REVIEW WILL BE ASSESSED.
 THIS IS ONLY NOTED AT THIS TIME.
  
 11) NOTE: PLEASE SEE THAT THIS BEING A CHANGE IN
 OCCUPANCY, PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS
 WHICH COMPLY WITH THE 2001 FBC CHAPTER 13.
 THIS WAS NOT SUBMITTED AS REQUIRED PER 415.ABCD AND
 415.2 ETC.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717