| 2007-02-11 14:48:09 | *** UNSAT 4TH REVIEW*** |
| | |
| | ** PLEASE SEE NOTES FROM PREVIOUS REVIEWS WHICH STILL |
| | NEED TO BE ADDRESSED ALONG WITH NEW NOTES AS STATED |
| | BELOW. |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE PLANS CONTAIN ALL THE RELEVANT |
| | CODES AND YEARS IN WHICH THE PLANS ARE DESIGNED UNDER. |
| | |
| | THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY |
| | OTHER TRADE. |
| | ** THIS IS UNDER THE 2001 FBC \ |
| | THE FOLLOWING MINIMUM CODES SHALL BE SHOWN ON PLANS |
| | WHICH ARE RELEVANT TO THE DESIGN OF PROJECT. |
| | 2001 FBC, 2002 NFPA-70(NEC), 2003 NFPA-101, 2002 |
| | NFPA-72 (WHERE APPLICABLE). |
| | |
| | 2 ) NOTE: PLEASE SHOW AND COMPLETE ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULE. |
| | THIS WAS STILL NOT DONE; THERE ARE SEVERAL ITEMS ON |
| | PLANS WHICH DO NOT CONTAIN CIRCUITS. PLEASE ALSO SEE |
| | CIRCUIT(S) ON PLANS WHICH DO NOT GO TO ANYTHING? PLEASE |
| | SEE THAT THE PANEL SCHEDULE SHALL BE SPECIFIC TO ALL |
| | CIRCUITS AND AREAS WHICH THEY FEED. PLEASE BE SURE THE |
| | CIRCUITS ON SCHEDULE CORRELATES TO THE PLANS FOR ANY |
| | ROOM AND AREA DESIGNATIONS. THIS REQUIRES THAT THE |
| | IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION. |
| | FBC104.3.1.1 ADMIN SECT 2001. |
| | NEC 408.4, 240.4, 310.16 |
| | |
| | 3) NOTE: PLEASE SEE 700.12E AS THE EM AND EXT LTS SHALL |
| | BE CIRCUITED TO THE BRANCH CIRCUIT LIGHTING IN ANY ONE |
| | AREA WHERE THESE FIXTURES ARE LOCATED. |
| | PLEASE ALSO SEE COMMENT WITH RESPECT TO FIXTURES AND |
| | TYPES. |
| | THIS COMMENT WAS MADE ON PREVIOUS REVIEW FOR |
| | CIRCUITING. |
| | |
| | 4) NOTE: PLEASE SHOW LOAD CALCULATIONS, WHICH ARE IN |
| | COMPLIANCE WITH THE 2002 NEC SECTION. 220. |
| | THIS WAS NOT DONE; THE CALCULATIONS SUBMITTED ARE NOT |
| | CODE COMPLIANT IN ANY FASHION. |
| | PLEASE INDICATE HOW LOADS WERE DERIVED ON A LOAD |
| | SUMMARY BASED FROM THE NEC. 220. |
| | 220.3,220.10,220.11,220.12 220.13, ALL CONTINUOUS LOADS |
| | 125% PER 215.3, 230.42 AND LARGEST MOTOR LOAD. PLEASE |
| | INCLUDE ALL EXISTING LOADS WITH NEW LOADS BEING ADDED. |
| | WHERE IS THE REST OF THE SERVICE FOR BUILDING WHICH |
| | THIS TENANT IS BEING ADDED TO EXISTING??? |
| | |
| | 5) NOTE: PLEASE CLARIFY MEANS OF EGRESS LIGHTING |
| | REQUIRED FOR REAR OF BLDG TO THE PUBLIC RIGHT OF WAY. |
| | THIS INCLUDES A BACK UP FIXTURE OF SOME TYPE. A NOTE ON |
| | PLANS WHICH MENTIONS LIGHTING TO BE INSTALLED DOES NOT |
| | COMPLY WITH SHOWING THE MINIMUM AS REQUIRED IN DESIGN. |
| | LS 101 2003, 7.8.1.3, 7.9.2.2. PLEASE KNOW, A MIN OF |
| | 10FT CANDLES IS REQUIRED UNDER NORMAL AND 1FT CANDLE |
| | UNDER EM CONDITIONS. PLEASE SHOW. |
| | |
| | 6) NOTE: PLEASE SEE NEW RISER SUBMITTED WHICH IS NOT |
| | CODE COMPLIANT. |
| | PLEASE SEE THE SERVICE ENTRANCE CONDUCTOR SIZES ALONG |
| | WITH FEEDERS ARE NOT OF SUFFICIENT SIZE TO CONFORM TO |
| | NEC 310.16. |
| | PLEASE SEE SOME OF THE CONDUCTOR SIZES AS SHOWN ARE NOT |
| | A STANDARD CONDUCTOR SIZE FROM THE STANDARDS OF AWG |
| | (AMERICAN WIRE GAUGE) OR NEC 310.16. |
| | PLEASE SEE SOME OF THE CONDUCTORS ARE ONLY RATED FOR |
| | 200AMPS. |
| | PLEASE SEE NOTE WHICH MENTIONS *TO PANEL POLE* ? WHAT |
| | IS THIS? |
| | PLEASE COMPLETE CONDUCTORS IN GUTTER AND THE REST OF |
| | THE SERVICE. PLEASE SHOW ON PLANS. |
| | PLEASE INDICATE SIZE OF METER CAN/SERVICE BEING |
| | PROVIDED. PLEASE SEE NOTE #4 ABOVE. |
| | |
| | ? PLEASE SEE 240.4, 230.2, 110.26, 240.24, 408.7, |
| | 215.5, 230.70, 240.6, ETC. |
| | ? THERE ARE TOO MANY SECTIONS TO LIST. |
| | |
| | |
| | 7) NOTE: PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTOR AFTER THE FIRST MEANS OF DISCONNECT. AS THE |
| | SERVICE SHOWN IS NOT CLEAR FOR THE REST OF THE SERVICE, |
| | IT IS UNCLEAR WHAT AND WHERE EQUIPMENT GROUNDS ARE FOR |
| | THE SERVICE AND HOW THEY ARE TO BE INSTALLED AS NOT |
| | OTHER EQUIPMENT IS BEING SHOWN FOR THE SERVICE. PLEASE |
| | SEE 250.66, 250.6, 250.24B, 250.110, 250.50, 250.104 |
| | AS THE GROUNDING ELECTRODE SYSTEM IS NOT COMPLETE AT |
| | THIS TIME. |
| | |
| | 8) NOTE: PLEASE PROVIDE AND A SYMBOL/FIXTURE LEGEND. |
| | UNABLE TO REVIEW FIXTURES FOR EM / EXT, ARE THESE COMBO |
| | UNITS?? |
| | |
| | 8) NOTE: PLEASE SHOW LOCATION OF THE EXISTING SERVICE. |
| | PLEASE ALSO SHOW AND INDICATE THE LOAD ON THE EXISTING |
| | SERVICE WITH NEW LOAD ADDED. AS NOTED ABOVE IN NOTE #4 |
| | AND NOTE #6. |
| | 220 NEC |
| | FBC ADMIN SECT 104.3.1.1 |
| | |
| | 9) NOTE: PLEASE SEE 424.3B FOR MIN OCP FOR AHU. PLEASE |
| | SEE NO MECH PLANS SUBMITTED, UNABLE TO VERIFY THE KW |
| | RATING OF THE HEAT. PLEASE VERIFY AS THE 6.5 AS SHOWN |
| | DOES NOT SEEM TO BE A TYPICAL SIZE? |
| | PLEASE SEE THIS IS THE SAME COMMENT FROM PREVIOUS |
| | REVIEW. |
| | |
| | 10) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE KNOW IF ANY |
| | OF THE NOTES ABOVE ARE NOTED ON THE FOLLOWING REVIEW |
| | FOR COMPLIANCE WHICH HAS NOT BEEN MADE, A FEE FOR PLAN |
| | REVIEW WILL BE ASSESSED. |
| | THIS IS ONLY NOTED AT THIS TIME. |
| | |
| | 11) NOTE: PLEASE SEE THAT THIS BEING A CHANGE IN |
| | OCCUPANCY, PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS |
| | WHICH COMPLY WITH THE 2001 FBC CHAPTER 13. |
| | THIS WAS NOT SUBMITTED AS REQUIRED PER 415.ABCD AND |
| | 415.2 ETC. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |