Plan Review Notes
Plan Review Notes For Permit 05061669
Permit Number 05061669
Review Stop P
Sequence Number 3
Notes
Date Text
2006-10-28 07:39:46PAUL SCHMITZ, PLUMBING & GAS PLANS
 EXAMINER561-805-6692
  
 [email protected]
 PLUMBING GAS PLAN REVIEW FBC 2001
  
 DENIED
  
 WHEN RESUBMITTING.
 PLEASE INCLUDE A RESPONCE LETTER INDICATING HOW THE
 ITEMS WERE ADDRESSED, THIS WILL HELP TO EXPIDITE THE
 PLAN REVIEW.
  
  
  
 (1)ADRESSED
  
 (2) CONTACT MS LYNN MASSON, WEST PALM
 BEACH ENVIROMENTAL COMPLIANCE
 FOR GREASE TRAP SIZING REQUIRMENTS.
 LOCAL ORDANCE. PHONE 561-822-2271
 NEW COMMENT, GREASE TRAP SIZE ON PLANS INCORRECT
  
 (3) CONTACT DEPT OF BUSINESS REGULATION
 HOTEL & RESTURANT DIVISION
 PROVIDE THEIR COMMENT SHEET AND TWO SETS
 OF STAMPED PLANS.
 NEW COMMENT,WORK SHEETS NOT INCLUDED.
  
 (4) ADDRESSED
  
 (5)PROVIDE A WATER RISER ISOMETRIC SHOWING
 ALL FIXTURE CONNECTIONS.BACK FLOW PREVENTER REQUIRED
 AT WATER METER.
  
 (6) NEW COMMENT PLUMBING ISOMETRIC DOES NOT MATCH FLOOR
 PLAN.
  
 (7) SHT 2,
 NOTES FROM PREVOIOUS PLAN REVIEWER, JOHN LEECH DENIED
  
 NEW COMMENTS;
 1.SHOW LOCATION OF WATER HEATER. IF WATER HEATER IS OUT
 SIDE IT MUST BE PROTECTED FROM THE WEATHER OR BE
 APPROVED BY THE MANUFATURE FOR OUT SIDE INSTALLATION.
  
 2.MOP SINK MUST GO TO GREASY WASTE.
  
 3.DISHWASHER MUST DISCHARGE INDIRECTLY TO , (FLOOR SINK
 )
  
 4.FLOOR SINK REQUIRED AT WAITRESS STATION FOR INDIRECT
 WASTE.
  
 5.THREE COMPARTMENT SINK SHOUD DISCHARGE TO A FLOOR
 SINK, SINK COULD BE USED FOR FOOD PREP. SEE PLUMBING
 CODE SEC. 802.1.1.
  
 END OF COMMENTS, QUESTIONS 561-805-6692