2007-07-09 17:52:12DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 FROM PREVIOUS REVIEWS: 4TH REVIEW
 *******FROM PREVIOUS REVIEWS:
  
  
 1. SHT P-1, GAS SYSTEM IS REQUIRED TO HAVE AN EMERGENCY
 SHUT OFF VALVE FOR COOKING EQUIPMENT. A SHUTOFF VALVE
 IS REQUIRED UPSTREAM OF THE EMERGENCY VALVE AND A UNION
 DOWNSTREAM, SO VALVE CAN BE REPLACED OR REPAIRED.
 ****RESPONSE NOTED, BUT THE FIRST VALVE, (MOST
 UPSTREAM), IS INDICATED AS THE EMERGENCY SHUT OFF
 VALVE. THEN THERE IS A GLOBE TYPE FITTING IDENTIFIED AS
 A UNION. SEE RED LINE EXAMPLE OF A MANUAL SHUT OFF
 VALVE, A UNION, THEN THE EMERGENCY SHUT OFF VALVE,
 (SOLINOID VALVE), IN THAT ORDER.
 *******RESPONSE NOTED AGAIN, BUT THE MANUAL SHUT OFF
 VALVE IS NOT SHOWN ON THE RISER DIAGRAM.
  
 1. OK
 3. OK
 4. OK
 5. OK
  
 6. SHT P-1, SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND/OR SYSTEM PER FBC-2001 FUEL GAS CODE
 APPENDIX A - USE OF CAPACITY TABLES (A)(3).
 ****RESPONSE NOTED, BUT THE INFORMATION IS NOT
 INDICATED ON THE PLANS. NOT ADDRESSED. ******RESPONSE
 NOTED, BUT THE DISTANCE IS NOT INDICATED ON SHT P-1.
  
 7. OK
  
 8. SHT P-1, SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND THE FBC-2001 FUEL GAS CODE SECTION 402.2.
 ****RESONSE NOTED, BUT THE INDICATE THE MODEL NUMBERS
 FOR THE GRIDDLE, THE RANGE, AND THE BOILER. THE BTU
 LOADS FOR THESE GAS APPLIANCES DO NOT REFLECT ANY OF
 THE MODEL NUMBERS SHOWN. THE MANUFACTURE SPECIFICATION
 SHEETS FOR THE GAS WATER HEATER HAVE NOT BEEN
 SUBMITTED.
 ******RESPONSE NOTED, BUT THIS HAS NOT BEEN ADDRESSED.
 THE BTU'S SHOWN ON THE RISER DIAGRAM DO NOT REFLECT THE
 BTU'S SHOWN ON THE MANUF. SPECIFICATION SHEETS AND THE
 MODELS ARE NOT INDICATED ON THE MANUF. SHEETS. STILL NO
 MANUF. SHEETS FOR THE WATER HEATER.
  
  
 ************NEW COMMENT**********
  
 1B. FOUR TIMES THE FEE WOULD HAVE BEEN ACCESSED ON THIS
 PLAN REVIEW IF ELECTRICAL PLAN REVIEWER HAD NOT ALREADY
 DONE SO. IF THE COMMENTS ARE NOT ADDRESSED WHEN
 RESUBMITTING NEXT TIME, ANOTHER FOUR TIMES THE FEE WILL
 BE ACCESS AGAIN ON THE NEXT RESUBMITTAL. FS
 533.80(2)(B).
  