| 2007-07-09 17:52:12 | DENIED |
| | REFERENCE: FBC-2001 FUEL GAS |
| | |
| | FROM PREVIOUS REVIEWS: 4TH REVIEW |
| | *******FROM PREVIOUS REVIEWS: |
| | |
| | |
| | 1. SHT P-1, GAS SYSTEM IS REQUIRED TO HAVE AN EMERGENCY |
| | SHUT OFF VALVE FOR COOKING EQUIPMENT. A SHUTOFF VALVE |
| | IS REQUIRED UPSTREAM OF THE EMERGENCY VALVE AND A UNION |
| | DOWNSTREAM, SO VALVE CAN BE REPLACED OR REPAIRED. |
| | ****RESPONSE NOTED, BUT THE FIRST VALVE, (MOST |
| | UPSTREAM), IS INDICATED AS THE EMERGENCY SHUT OFF |
| | VALVE. THEN THERE IS A GLOBE TYPE FITTING IDENTIFIED AS |
| | A UNION. SEE RED LINE EXAMPLE OF A MANUAL SHUT OFF |
| | VALVE, A UNION, THEN THE EMERGENCY SHUT OFF VALVE, |
| | (SOLINOID VALVE), IN THAT ORDER. |
| | *******RESPONSE NOTED AGAIN, BUT THE MANUAL SHUT OFF |
| | VALVE IS NOT SHOWN ON THE RISER DIAGRAM. |
| | |
| | 1. OK |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | |
| | 6. SHT P-1, SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE OUTLET IN THE |
| | BUILDING AND/OR SYSTEM PER FBC-2001 FUEL GAS CODE |
| | APPENDIX A - USE OF CAPACITY TABLES (A)(3). |
| | ****RESPONSE NOTED, BUT THE INFORMATION IS NOT |
| | INDICATED ON THE PLANS. NOT ADDRESSED. ******RESPONSE |
| | NOTED, BUT THE DISTANCE IS NOT INDICATED ON SHT P-1. |
| | |
| | 7. OK |
| | |
| | 8. SHT P-1, SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND THE FBC-2001 FUEL GAS CODE SECTION 402.2. |
| | ****RESONSE NOTED, BUT THE INDICATE THE MODEL NUMBERS |
| | FOR THE GRIDDLE, THE RANGE, AND THE BOILER. THE BTU |
| | LOADS FOR THESE GAS APPLIANCES DO NOT REFLECT ANY OF |
| | THE MODEL NUMBERS SHOWN. THE MANUFACTURE SPECIFICATION |
| | SHEETS FOR THE GAS WATER HEATER HAVE NOT BEEN |
| | SUBMITTED. |
| | ******RESPONSE NOTED, BUT THIS HAS NOT BEEN ADDRESSED. |
| | THE BTU'S SHOWN ON THE RISER DIAGRAM DO NOT REFLECT THE |
| | BTU'S SHOWN ON THE MANUF. SPECIFICATION SHEETS AND THE |
| | MODELS ARE NOT INDICATED ON THE MANUF. SHEETS. STILL NO |
| | MANUF. SHEETS FOR THE WATER HEATER. |
| | |
| | |
| | ************NEW COMMENT********** |
| | |
| | 1B. FOUR TIMES THE FEE WOULD HAVE BEEN ACCESSED ON THIS |
| | PLAN REVIEW IF ELECTRICAL PLAN REVIEWER HAD NOT ALREADY |
| | DONE SO. IF THE COMMENTS ARE NOT ADDRESSED WHEN |
| | RESUBMITTING NEXT TIME, ANOTHER FOUR TIMES THE FEE WILL |
| | BE ACCESS AGAIN ON THE NEXT RESUBMITTAL. FS |
| | 533.80(2)(B). |
| | |