Plan Review Notes
Plan Review Notes For Permit 05061669
Permit Number 05061669
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2006-10-31 15:43:08***DENIED***
  
 PLEASE NOTE THAT IT DOES NOT APPEAR THAT THE LAST FIRE
 REVIEW HAS BEEN ADDRESSED. PLEASE SEE THE FOLLOWING
 TAKEN DIRECTLY FROM THE LAST FIRE REVIEW:
  
 1) SEPARATE PLANS AND PERMITS REQUIRED FOR HOOD, DUCT
 AND SUPPRESSION SYSTEMS.
  
 2) PLANS MAKE REFERENCE TO A CO2 SYSTEM. THE PLANS
 SHOULD REFERENCE A WET CHEMICAL SYSTEM THAT COMPLIES
 WITH UL 300.
  
 3) A SINGLE STAIR IS DISPLAYED ON THE NORTH ELEVATION
 WHICH IS IN CLOSE PROXIMITY TO DOORS AND WINDOWS. DO
 ANY OTHER EXITS EXIST FROM THE UPSTAIRS APARTMENTS? IF
 NOT, A SINGLE MEANS OF EGRESS IS SHOWN WITH UNPROTECTED
 OPENINGS WITHIN (10) FEET OF THESE STAIRS. PLEASE
 ADVISE.
  
 PLEASE PROVIDE COMMENTS AS THIS WILL HELP EXPEDITE THIS
 PROCESS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722 OR 804-4756