| Plan Review Notes For Permit 05061669 |
| Permit Number |
05061669 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-10-31 15:43:08 | ***DENIED*** | | | | | | PLEASE NOTE THAT IT DOES NOT APPEAR THAT THE LAST FIRE | | | REVIEW HAS BEEN ADDRESSED. PLEASE SEE THE FOLLOWING | | | TAKEN DIRECTLY FROM THE LAST FIRE REVIEW: | | | | | | 1) SEPARATE PLANS AND PERMITS REQUIRED FOR HOOD, DUCT | | | AND SUPPRESSION SYSTEMS. | | | | | | 2) PLANS MAKE REFERENCE TO A CO2 SYSTEM. THE PLANS | | | SHOULD REFERENCE A WET CHEMICAL SYSTEM THAT COMPLIES | | | WITH UL 300. | | | | | | 3) A SINGLE STAIR IS DISPLAYED ON THE NORTH ELEVATION | | | WHICH IS IN CLOSE PROXIMITY TO DOORS AND WINDOWS. DO | | | ANY OTHER EXITS EXIST FROM THE UPSTAIRS APARTMENTS? IF | | | NOT, A SINGLE MEANS OF EGRESS IS SHOWN WITH UNPROTECTED | | | OPENINGS WITHIN (10) FEET OF THESE STAIRS. PLEASE | | | ADVISE. | | | | | | PLEASE PROVIDE COMMENTS AS THIS WILL HELP EXPEDITE THIS | | | PROCESS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW (561) 805-6722 OR 804-4756 |
|