Plan Review Notes
Plan Review Notes For Permit 05061669
Permit Number 05061669
Review Stop E
Sequence Number 3
Notes
Date Text
2006-10-15 09:16:51**** UNSAT *****
  
 ** THIS IS UNDER THE 2001 FBC \
 THE FOLLOWING MINIMUM CODES SHALL BE SHOWN ON PLANS
 WHICH ARE RELEVANT TO THE DESIGN OF PROJECT.
 2001 FBC, 2002 NFPA-70(NEC), 2003 NFPA-101, 2002
 NFPA-72 (IF APPLICABLE).
  
 ** PLEASE SEE SOME COMMENTS FROM REVIEW DATED 7/6/05 BY
 THIS REVIEWER ARE STILL IN NEED OF ADDRESSING. PLEASE
 ALSO SEE SOME NEW COMMENTS BASED ON PLANS SUBMITTED.
  
 1) NOTE: PLEASE SHOW AND COMPLETE ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULE.
  
 PREVIOUS REVIEW#1
 FBC104.3.1.1 ADMIN SECT 2001.
  
 2) NOTE: PLEASE SEE 700.12E AS THE EM AND EXT LTS SHALL
 BE CIRCUITED TO THE BRANCH CIRCUIT LIGHTING IN ANY ONE
 AREA WHERE THESE FIXTURES ARE LOCATED.
 PLEASE ALSO SEE COMMENT WITH RESPECT TO FIXTURES AND
 TYPES.
 PREVIOUS REVIEW#1
  
 3) NOTE: PLEASE SHOW LOAD CALCULATIONS, PLEASE INDICATE
 HOW LOADS WERE DERIVED ON A LOAD SUMMARY BASED FROM THE
 NEC. 220. 220.3,220.10,220.11,220.13, ALL CONTINUOUS
 LOADS 125% PER 215.3, 230.42 AND LARGEST MOTOR LOAD.
 PREVIOUS REVIEW.#1
  
 4) NOTE: PLEASE SEE CU'S AND POSSIBLE MISSING
 DISCONNECTS, GFI RECEPT. 440.11,110.26, 210.63 PREVIOUS
 REVIEW #1
  
 5) NOTE: PLEASE CLARIFY MEANS OF EGRESS LIGHTING
 REQUIRED FOR REAR OF BLDG TO THE PUBLIC RIGHT OF WAY.
 THIS INCLUDES A BACK UP FIXTURE OF SOME TYPE.
 LS 101 2003, 7.8.1.3, 7.9.2.2. PLEASE KNOW, A MIN OF
 10FT CANDLES IS REQUIRED UNDER NORMAL AND 1FT CANDLE
 UNDER EM CONDITIONS. PLEASE SHOW.
  
 6) NOTE: PLEASE COMPLETE PANEL SCHEDULE AS ITEM SHOWN,
 HOWEVER NO LOADS OR OCP ETC.
 408.4,310.16
  
 7) NOTE: PLEASE PROVIDE AND A SYMBOL/FIXTURE LEGEND.
 UNABLE TO REVIEW FIXTURES FOR EM / EXT, ARE THESE COMBO
 UNITS??
  
 8) NOTE: PLEASE SHOW LOCATION OF THE EXISTING SERVICE.
 PLEASE ALSO SHOW AND INDICATE THE LOAD ON THE EXISTING
 SERVICE WITH NEW LOAD ADDED.
 220 NEC
 FBC ADMIN SECT 104.3.1.1
  
 9) NOTE: PLEASE SEE E424.3B FOR MIN OCP FOR AHU. PLEASE
 SEE NO MECH PLANS SUBMITTED, UNABLE TO VERIFY THE KW
 RATING OF THE HEAT. PLEASE VERIFY AS THE 6.5 AS SHOWN
 DOES NOT SEEM TO BE A TYPICAL SIZE?
  
 10) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. AS THIS REVIEWER
 DID NOT REVIEW THE 2ND SET OF SUBMITTED PLANS, THIS IS
 ONLY A NOTICE GIVEN AT THIS TIME.
  
 ** PLEASE KNOW, AS ELECTRICAL PLUMB BLDG ETC IS MIXED
 AND NOT ON SEPARATE PLANS/SHEETS, EVEN IF SHEETS ARE
 PASSED BY OTHER REVIEWERS, THEY MAY BE VOID DUE TO THE
 CONTENT OF MORE THAN ONE TRADE ON ONE SHEET.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  