| 2006-10-15 09:16:51 | **** UNSAT ***** |
| | |
| | ** THIS IS UNDER THE 2001 FBC \ |
| | THE FOLLOWING MINIMUM CODES SHALL BE SHOWN ON PLANS |
| | WHICH ARE RELEVANT TO THE DESIGN OF PROJECT. |
| | 2001 FBC, 2002 NFPA-70(NEC), 2003 NFPA-101, 2002 |
| | NFPA-72 (IF APPLICABLE). |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM REVIEW DATED 7/6/05 BY |
| | THIS REVIEWER ARE STILL IN NEED OF ADDRESSING. PLEASE |
| | ALSO SEE SOME NEW COMMENTS BASED ON PLANS SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SHOW AND COMPLETE ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULE. |
| | |
| | PREVIOUS REVIEW#1 |
| | FBC104.3.1.1 ADMIN SECT 2001. |
| | |
| | 2) NOTE: PLEASE SEE 700.12E AS THE EM AND EXT LTS SHALL |
| | BE CIRCUITED TO THE BRANCH CIRCUIT LIGHTING IN ANY ONE |
| | AREA WHERE THESE FIXTURES ARE LOCATED. |
| | PLEASE ALSO SEE COMMENT WITH RESPECT TO FIXTURES AND |
| | TYPES. |
| | PREVIOUS REVIEW#1 |
| | |
| | 3) NOTE: PLEASE SHOW LOAD CALCULATIONS, PLEASE INDICATE |
| | HOW LOADS WERE DERIVED ON A LOAD SUMMARY BASED FROM THE |
| | NEC. 220. 220.3,220.10,220.11,220.13, ALL CONTINUOUS |
| | LOADS 125% PER 215.3, 230.42 AND LARGEST MOTOR LOAD. |
| | PREVIOUS REVIEW.#1 |
| | |
| | 4) NOTE: PLEASE SEE CU'S AND POSSIBLE MISSING |
| | DISCONNECTS, GFI RECEPT. 440.11,110.26, 210.63 PREVIOUS |
| | REVIEW #1 |
| | |
| | 5) NOTE: PLEASE CLARIFY MEANS OF EGRESS LIGHTING |
| | REQUIRED FOR REAR OF BLDG TO THE PUBLIC RIGHT OF WAY. |
| | THIS INCLUDES A BACK UP FIXTURE OF SOME TYPE. |
| | LS 101 2003, 7.8.1.3, 7.9.2.2. PLEASE KNOW, A MIN OF |
| | 10FT CANDLES IS REQUIRED UNDER NORMAL AND 1FT CANDLE |
| | UNDER EM CONDITIONS. PLEASE SHOW. |
| | |
| | 6) NOTE: PLEASE COMPLETE PANEL SCHEDULE AS ITEM SHOWN, |
| | HOWEVER NO LOADS OR OCP ETC. |
| | 408.4,310.16 |
| | |
| | 7) NOTE: PLEASE PROVIDE AND A SYMBOL/FIXTURE LEGEND. |
| | UNABLE TO REVIEW FIXTURES FOR EM / EXT, ARE THESE COMBO |
| | UNITS?? |
| | |
| | 8) NOTE: PLEASE SHOW LOCATION OF THE EXISTING SERVICE. |
| | PLEASE ALSO SHOW AND INDICATE THE LOAD ON THE EXISTING |
| | SERVICE WITH NEW LOAD ADDED. |
| | 220 NEC |
| | FBC ADMIN SECT 104.3.1.1 |
| | |
| | 9) NOTE: PLEASE SEE E424.3B FOR MIN OCP FOR AHU. PLEASE |
| | SEE NO MECH PLANS SUBMITTED, UNABLE TO VERIFY THE KW |
| | RATING OF THE HEAT. PLEASE VERIFY AS THE 6.5 AS SHOWN |
| | DOES NOT SEEM TO BE A TYPICAL SIZE? |
| | |
| | 10) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. AS THIS REVIEWER |
| | DID NOT REVIEW THE 2ND SET OF SUBMITTED PLANS, THIS IS |
| | ONLY A NOTICE GIVEN AT THIS TIME. |
| | |
| | ** PLEASE KNOW, AS ELECTRICAL PLUMB BLDG ETC IS MIXED |
| | AND NOT ON SEPARATE PLANS/SHEETS, EVEN IF SHEETS ARE |
| | PASSED BY OTHER REVIEWERS, THEY MAY BE VOID DUE TO THE |
| | CONTENT OF MORE THAN ONE TRADE ON ONE SHEET. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |