| Date |
Text |
| 2006-10-18 14:25:07 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | NOTE - NEW PLANS FROM A NEW DESIGN |
| | PROFESSIONAL, 2ND REVIEW FOR THIS DOR |
| | |
| | WHEN RESUBMITTING,PLEASE INCLUDE A RESPONSE LETTER |
| | INDICATING HOW THE ITEMS WERE ADDRESSED.SOME |
| | QUESTIONS WERE NOT ANSWERED. |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1.) ADDRESSED. |
| | |
| | 2.) IMPACT FEES MAY BE DUE (CHANGE OF |
| | USE).THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 |
| | |
| | 2ND REVIEW - THE RECEIPT WAS IN THE PACKAGE BUT THE |
| | PLANS WERE NOT STAMPED.WHEN |
| | RESUBMITTING, PLEASE BE SURE THAT BOTH |
| | ITEMS ARE INCLUDED. |
| | |
| | 3RD REVIEW - THE RECEIPT AND THE STAMPED PLAN ARE |
| | REQUIRED, NEITHER ARE IN THE PACKAGE. |
| | |
| | 3. - 7.)ADDRESSED. |
| | |
| | 8.-12.)ADDRESSED. |
| | |
| | 13.)SHOW COMPLIANCE WITH FBC1007, ALL |
| | DETAILS - STAIR WIDTH, TREAD AND RISER |
| | DIMENSIONS FBC1007, ALL REQUIREMENTS OF |
| | FBC1006.2, HANDRAIL AND GUARDRAIL |
| | DIMENSIONS FBC1007 AND FBC1015, HANDRAIL |
| | AND GUARDRAIL DESIGN CRITERIA (FBC1608). |
| | |
| | THIS WAS ADDRESSED BUT THE STAIRRAIL IS NOT COMPLIANT. |
| | STAIR RISER APPEARS NON COMPLIANT.AS AREA HAS NOT |
| | BEEN PROPERLY CLASSIFIED, CODE COMPLIANCE CANNOT BE |
| | DETERMINED. |
| | |
| | 14. - 15.)ADDRESSED. |
| | |
| | 16-17.)ADDRESSED. |
| | |
| | 18.)N/A, NO LONGER CALLED A MEZZANINE. |
| | |
| | 19.)SHOW FIRE RATING REQUIREMENT FOR |
| | THE DOORS WITHIN 10FT OF THE STAIRS, |
| | FBC705.1.2.PROVIDE FIRE RATING |
| | INFORMATION FOR THE SPECIFIC DOOR YOU |
| | ARE INSTALLING. |
| | |
| | 20.)SHOW ALL DETAILS AND DESIGN LOAD REQUIREMENTS FOR |
| | THE MEZZANINE.WAS THE |
| | ORIGINAL MEZZANINE PERMITTED LIKE THIS? |
| | |
| | THE AREA IS NOW CALLED AN "ATTIC", PLEASE SEE ITEM 29. |
| | DESIGN LOADS NOT PROVIDED. SHOW DESIGN LOADS FOR THIS |
| | AREA, REGARDLESS OF WHAT IT IS LABELED; FBC TABLE |
| | 1604.1. |
| | |
| | 21.)PROVIDE AREA CALCULATIONS FOR THE |
| | SPACE.IT IS NOT CLEAR IF THE MEZZANINE |
| | WAS INCLUDED WHEN IMPACT FEES WERE PAID. |
| | |
| | 3RD REVIEW - AREA NOW CALLED ATTIC, PROVIDE AREA. |
| | |
| | 22.)PROVIDE WIND DESIGN CRITERIA |
| | REQUIRED BY FBC1606.1.7. |
| | |
| | 3RD REVEIW - WRONG CODE SPECIFIED BASED ON APPLLICATION |
| | DATE. |
| | |
| | DECLARE A GOVERNING CODE ON THE PLAN.IF YOU WISH AT |
| | THIS TIME TO SWITCH TO FBC2004, RESUBMIT WITH NEW |
| | APPLICATOIN. |
| | |
| | PLAN STATES C&C DESIGN PRESSURES, "SEE PLAN", CANNOT |
| | LOCATE ON THIS PLAN. |
| | |
| | 23-24.)ADDRESSED. |
| | |
| | 25.)PREVIOUS PLANS MADE REFERENCE TO |
| | ACCESSING THE MEZZANINE FROM THE OTHER |
| | TENANT SPACE.WHAT HAPPENED TO THIS |
| | OPENING, NO LONGER SHOWN ON THE PLAN? |
| | |
| | 26.)OLD PLANS SHOWNO LANDING ON THE |
| | STAIRS, THIS PLAN SHOWS A LANDING. |
| | ADDRESS. |
| | |
| | 27.)SHOW REQUIRED TENANT/OCCUPANCY |
| | SEPARATION BETWEEN THE LAUNDROMAT AND |
| | THE RESTAURANT.DECLARE AN OCCUPANCY |
| | FOR THE RESTAURANT. |
| | |
| | NOT ADDRESSED.THE SEPARATION BETWEEN THE RESTAURANT |
| | AND THE 2ND FLOOR STATES 5/8 TYPE X DRYWALL, DOES NOT |
| | STATE HOW MANY LAYERS.YOU SPECIFY A 1 HOUR, BUT 5/8 |
| | TYPE X IS 40 MINUTES. |
| | |
| | 28.)SEE ATTACHED FS553.80(2)(B). |
| | |
| | NEW COMMENT: |
| | |
| | 29.)THE MECHANICAL ROOM IS NOT AN ATTIC, SEE |
| | DEFINITIONS FBC13-202.IS THIS A MEZZANINE?TO BE |
| | TREATED AS ANOTHER FLOOR?CODE COMPLIANCE CANNOT BE |
| | DETERMINED UNTIL DOR DETERMINES HOW TO CLASSIFY THE |
| | SPACE.NOTE THAT A NEW AREA IS BEING CREATED AND A |
| | CODE COMPLIANT MEANS OF EGRESS MUST SERVE THAT AREA. |
| | SHEET 5 STILL CALLS IT A MEZZANINE. |
| | |
| | 30.)SHOW HEIGHT OF THE DOOR AT THE LANDING. |
| | |
| | 31.)THE PLAN SHOWS A MECHANICAL PLATFORM OUTSIDE OF |
| | THE BUILDING, "8' ANDER THE BUILDING".PROVIDE A |
| | COMPLETE DETAIL INCLUDING DESIGN LOAD CRITERIA.PLAN |
| | STATES "SEE DETAIL 1", CANNOT LOCATED. ZONING REVIEW |
| | REQUIRED. |
| | |
| | 32.)PRODUCT APPROVALS SUBMITTED ARE FOR NON IMPACT |
| | WITH SHUTTERS.USE OF REMOVABLE SHUTTERS MUST BE |
| | APPROVED BY THE BUILDING OFFICIAL, SEE ATTACHED POLICY, |
| | ITEM 13. |