Plan Review Notes
Plan Review Notes For Permit 05061669
Permit Number 05061669
Review Stop B
Sequence Number 3
Notes
Date Text
2006-10-18 14:25:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 NOTE - NEW PLANS FROM A NEW DESIGN
 PROFESSIONAL, 2ND REVIEW FOR THIS DOR
  
 WHEN RESUBMITTING,PLEASE INCLUDE A RESPONSE LETTER
 INDICATING HOW THE ITEMS WERE ADDRESSED.SOME
 QUESTIONS WERE NOT ANSWERED.
  
 FROM PREVIOUS LIST:
  
 1.) ADDRESSED.
  
 2.) IMPACT FEES MAY BE DUE (CHANGE OF
 USE).THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 2ND REVIEW - THE RECEIPT WAS IN THE PACKAGE BUT THE
 PLANS WERE NOT STAMPED.WHEN
 RESUBMITTING, PLEASE BE SURE THAT BOTH
 ITEMS ARE INCLUDED.
  
 3RD REVIEW - THE RECEIPT AND THE STAMPED PLAN ARE
 REQUIRED, NEITHER ARE IN THE PACKAGE.
  
 3. - 7.)ADDRESSED.
  
 8.-12.)ADDRESSED.
  
 13.)SHOW COMPLIANCE WITH FBC1007, ALL
 DETAILS - STAIR WIDTH, TREAD AND RISER
 DIMENSIONS FBC1007, ALL REQUIREMENTS OF
 FBC1006.2, HANDRAIL AND GUARDRAIL
 DIMENSIONS FBC1007 AND FBC1015, HANDRAIL
 AND GUARDRAIL DESIGN CRITERIA (FBC1608).
  
 THIS WAS ADDRESSED BUT THE STAIRRAIL IS NOT COMPLIANT.
 STAIR RISER APPEARS NON COMPLIANT.AS AREA HAS NOT
 BEEN PROPERLY CLASSIFIED, CODE COMPLIANCE CANNOT BE
 DETERMINED.
  
 14. - 15.)ADDRESSED.
  
 16-17.)ADDRESSED.
  
 18.)N/A, NO LONGER CALLED A MEZZANINE.
  
 19.)SHOW FIRE RATING REQUIREMENT FOR
 THE DOORS WITHIN 10FT OF THE STAIRS,
 FBC705.1.2.PROVIDE FIRE RATING
 INFORMATION FOR THE SPECIFIC DOOR YOU
 ARE INSTALLING.
  
 20.)SHOW ALL DETAILS AND DESIGN LOAD REQUIREMENTS FOR
 THE MEZZANINE.WAS THE
 ORIGINAL MEZZANINE PERMITTED LIKE THIS?
  
 THE AREA IS NOW CALLED AN "ATTIC", PLEASE SEE ITEM 29.
 DESIGN LOADS NOT PROVIDED. SHOW DESIGN LOADS FOR THIS
 AREA, REGARDLESS OF WHAT IT IS LABELED; FBC TABLE
 1604.1.
  
 21.)PROVIDE AREA CALCULATIONS FOR THE
 SPACE.IT IS NOT CLEAR IF THE MEZZANINE
 WAS INCLUDED WHEN IMPACT FEES WERE PAID.
  
 3RD REVIEW - AREA NOW CALLED ATTIC, PROVIDE AREA.
  
 22.)PROVIDE WIND DESIGN CRITERIA
 REQUIRED BY FBC1606.1.7.
  
 3RD REVEIW - WRONG CODE SPECIFIED BASED ON APPLLICATION
 DATE.
  
 DECLARE A GOVERNING CODE ON THE PLAN.IF YOU WISH AT
 THIS TIME TO SWITCH TO FBC2004, RESUBMIT WITH NEW
 APPLICATOIN.
  
 PLAN STATES C&C DESIGN PRESSURES, "SEE PLAN", CANNOT
 LOCATE ON THIS PLAN.
  
 23-24.)ADDRESSED.
  
 25.)PREVIOUS PLANS MADE REFERENCE TO
 ACCESSING THE MEZZANINE FROM THE OTHER
 TENANT SPACE.WHAT HAPPENED TO THIS
 OPENING, NO LONGER SHOWN ON THE PLAN?
  
 26.)OLD PLANS SHOWNO LANDING ON THE
 STAIRS, THIS PLAN SHOWS A LANDING.
 ADDRESS.
  
 27.)SHOW REQUIRED TENANT/OCCUPANCY
 SEPARATION BETWEEN THE LAUNDROMAT AND
 THE RESTAURANT.DECLARE AN OCCUPANCY
 FOR THE RESTAURANT.
  
 NOT ADDRESSED.THE SEPARATION BETWEEN THE RESTAURANT
 AND THE 2ND FLOOR STATES 5/8 TYPE X DRYWALL, DOES NOT
 STATE HOW MANY LAYERS.YOU SPECIFY A 1 HOUR, BUT 5/8
 TYPE X IS 40 MINUTES.
  
 28.)SEE ATTACHED FS553.80(2)(B).
  
 NEW COMMENT:
  
 29.)THE MECHANICAL ROOM IS NOT AN ATTIC, SEE
 DEFINITIONS FBC13-202.IS THIS A MEZZANINE?TO BE
 TREATED AS ANOTHER FLOOR?CODE COMPLIANCE CANNOT BE
 DETERMINED UNTIL DOR DETERMINES HOW TO CLASSIFY THE
 SPACE.NOTE THAT A NEW AREA IS BEING CREATED AND A
 CODE COMPLIANT MEANS OF EGRESS MUST SERVE THAT AREA.
 SHEET 5 STILL CALLS IT A MEZZANINE.
  
 30.)SHOW HEIGHT OF THE DOOR AT THE LANDING.
  
 31.)THE PLAN SHOWS A MECHANICAL PLATFORM OUTSIDE OF
 THE BUILDING, "8' ANDER THE BUILDING".PROVIDE A
 COMPLETE DETAIL INCLUDING DESIGN LOAD CRITERIA.PLAN
 STATES "SEE DETAIL 1", CANNOT LOCATED. ZONING REVIEW
 REQUIRED.
  
 32.)PRODUCT APPROVALS SUBMITTED ARE FOR NON IMPACT
 WITH SHUTTERS.USE OF REMOVABLE SHUTTERS MUST BE
 APPROVED BY THE BUILDING OFFICIAL, SEE ATTACHED POLICY,
 ITEM 13.