| 2006-03-10 00:00:00 | DENIED; |
| | ITEMS NOT COVERED FROM FIRST REVIEW; |
| | COMMENT #2 CONTACT MS LYNN MASSON, WEST |
| | PALM BEACH ENVIROMENT COMPLIANCE FOR |
| | GREASE TRAP SIZING REQUIRMENTS. LOCAL |
| | ORDANCE. PHONE (561) 822-2271. |
| | COMMENT # 3 HOTEL AND RESTURANT DIVISION |
| | WORK SHEETS WERE NOT ATACHED TO PLANS. |
| | COMMENT # 4 DISHWASHER TO DRAIN TO |
| | SANITARY SEWER (NOT SHOWN ON RISER |
| | DIAGRAM. WATER RISER DIAGRAM NOT SHOWN. |
| | BACKFLOW NOT SHOWN ON PLANS. |
| | COMMENT # 5 GAS REQUIREMENTS, TYPE OF |
| | GAS NATURAL OR L.P., LIST TOTAL BTU'S |
| | AND LONGEST RUN. END OF COMMENTS FROM |
| | FIRST REVIEW. |
| | NEW COMMENTS; |
| | 1.SHOW LOCATION OF WATER HEATER. IF |
| | WATER HEATER IS OUT SIDE IT MUST BE |
| | PROTECTED FROM THE WEATHER OR BE |
| | APPROVED BY THE MANUFATURE FOR OUT SIDE |
| | INSTALLATION. |
| | 2.MOP SINK MUST GO TO GREASY WASTE. |
| | 3.DISHWASHER MUST DISCHARGE INDIRECTLY |
| | TO SANITARY, (FLOOR SINK REQUIRED) |
| | 4.FLOOR SINK REQUIRED AT WAITRESS |
| | STATION FOR INDIRECT WASTE. |
| | 5.THREE COMPARTMENT SINK SHOUD DISCHARGE |
| | TO A FLOOR SINK, SINK COULD BE USED FOR |
| | FOOD PREP. SEE PLUMBING CODE SEC. |
| | 802.1.1. |
| | 6.GAS SYSTEM IS REQUIRED TO HAVE A |
| | EMERGENCY SHUT OFF VALVE FOR COOKING |
| | EQUIPMENT. A SHUTOFF VALVE IS REQUIRED |
| | UP STREAM STREAM OF THE EMERGENCY VALVE |
| | AND A UNION DOWN STREAM SO VALVE CAN BE |
| | REPLACED OR REPAIRED. |
| | PLUMBING PLAN REVIEW BY; |
| | JOHN LEECH |