| 2007-02-27 11:10:59 | DENIED |
| | REFERENCE: FBC-2001 FUEL GAS |
| | |
| | FROM PREVIOUS REVIEWS: 4TH REVIEW |
| | |
| | 1. SHT P-1, GAS SYSTEM IS REQUIRED TO HAVE AN EMERGENCY |
| | SHUT OFF VALVE FOR COOKING EQUIPMENT. A SHUTOFF VALVE |
| | IS REQUIRED UPSTREAM OF THE EMERGENCY VALVE AND A UNION |
| | DOWNSTREAM, SO VALVE CAN BE REPLACED OR REPAIRED. |
| | ****RESPONSE NOTED, BUT THE FIRST VALVE, (MOST |
| | UPSTREAM), IS INDICATED AS THE EMERGENCY SHUT OFF |
| | VALVE. THEN THERE IS A GLOBE TYPE FITTING IDENTIFIED AS |
| | A UNION. SEE RED LINE EXAMPLE OF A MANUAL SHUT OFF |
| | VALVE, A UNION, THEN THE EMERGENCY SHUT OFF VALVE, |
| | (SOLINOID VALVE), IN THAT ORDER. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | ****RESPONSE NOTED, BUT THERE ARE SECTIONS THAT SHOW NO |
| | LENGTH MEASUREMENT. SHOW THE DISTANCE FROM THE METER TO |
| | FIRST RISER, THE DISTANCE FROM THE BOTTOM OF THE FIRST |
| | RISER TO THE TOP, AND FROM THE TOP OF THE FIRST RISER |
| | TO THE START OF THE 7'0" LENGTH OF PIPE IN THE CEILING. |
| | (SEE HIGHLIGHTED SECTIONS ON ONE SET OF PLANS). |
| | |
| | 3. OK |
| | |
| | 4. SHT P-1 TYPE OF GAS, (LP OR NATURAL) ****RESPONSE |
| | NOTED, BUT PLEASE INDICATE ON THE PLANS. |
| | |
| | 5. OK |
| | |
| | 6. SHT P-1, SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE OUTLET IN THE |
| | BUILDING AND/OR SYSTEM PER FBC-2001 FUEL GAS CODE |
| | APPENDIX A - USE OF CAPACITY TABLES (A)(3). |
| | ****RESPONSE NOTED, BUT THE INFORMATION IS NOT |
| | INDICATED ON THE PLANS. NOT ADDRESSED. |
| | |
| | 7. OK |
| | |
| | 8. SHT P-1, SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND THE FBC-2001 FUEL GAS CODE SECTION 402.2. |
| | ****RESONSE NOTED, BUT THE INDICATE THE MODEL NUMBERS |
| | FOR THE GRIDDLE, THE RANGE, AND THE BOILER. THE BTU |
| | LOADS FOR THESE GAS APPLIANCES DO NOT REFLECT ANY OF |
| | THE MODEL NUMBERS SHOWN. THE MANUFACTURE SPECIFICATION |
| | SHEETS FOR THE GAS WATER HEATER HAVE NOT BEEN |
| | SUBMITTED. |
| | |
| | REVIEW BY KEN STEVENS |