2007-02-27 11:10:59DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 FROM PREVIOUS REVIEWS: 4TH REVIEW
  
 1. SHT P-1, GAS SYSTEM IS REQUIRED TO HAVE AN EMERGENCY
 SHUT OFF VALVE FOR COOKING EQUIPMENT. A SHUTOFF VALVE
 IS REQUIRED UPSTREAM OF THE EMERGENCY VALVE AND A UNION
 DOWNSTREAM, SO VALVE CAN BE REPLACED OR REPAIRED.
 ****RESPONSE NOTED, BUT THE FIRST VALVE, (MOST
 UPSTREAM), IS INDICATED AS THE EMERGENCY SHUT OFF
 VALVE. THEN THERE IS A GLOBE TYPE FITTING IDENTIFIED AS
 A UNION. SEE RED LINE EXAMPLE OF A MANUAL SHUT OFF
 VALVE, A UNION, THEN THE EMERGENCY SHUT OFF VALVE,
 (SOLINOID VALVE), IN THAT ORDER.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT THERE ARE SECTIONS THAT SHOW NO
 LENGTH MEASUREMENT. SHOW THE DISTANCE FROM THE METER TO
 FIRST RISER, THE DISTANCE FROM THE BOTTOM OF THE FIRST
 RISER TO THE TOP, AND FROM THE TOP OF THE FIRST RISER
 TO THE START OF THE 7'0" LENGTH OF PIPE IN THE CEILING.
 (SEE HIGHLIGHTED SECTIONS ON ONE SET OF PLANS).
  
 3. OK
  
 4. SHT P-1 TYPE OF GAS, (LP OR NATURAL) ****RESPONSE
 NOTED, BUT PLEASE INDICATE ON THE PLANS.
  
 5. OK
  
 6. SHT P-1, SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND/OR SYSTEM PER FBC-2001 FUEL GAS CODE
 APPENDIX A - USE OF CAPACITY TABLES (A)(3).
 ****RESPONSE NOTED, BUT THE INFORMATION IS NOT
 INDICATED ON THE PLANS. NOT ADDRESSED.
  
 7. OK
  
 8. SHT P-1, SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND THE FBC-2001 FUEL GAS CODE SECTION 402.2.
 ****RESONSE NOTED, BUT THE INDICATE THE MODEL NUMBERS
 FOR THE GRIDDLE, THE RANGE, AND THE BOILER. THE BTU
 LOADS FOR THESE GAS APPLIANCES DO NOT REFLECT ANY OF
 THE MODEL NUMBERS SHOWN. THE MANUFACTURE SPECIFICATION
 SHEETS FOR THE GAS WATER HEATER HAVE NOT BEEN
 SUBMITTED.
  