Plan Review Notes
Plan Review Notes For Permit 05061669
Permit Number 05061669
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-02-15 00:00:001. SEPARATE PLANS AND PERMITS REQUIRED
 FOR HOOD, DUCT, AND SUPPRESSION SYSTEM.
  
 2. PLANS MAKE REFERENCE TO A CO2 SYSTEM.
 THE PLANS SHOULD REFERENCE A WET
 CHEMICAL SYSTEM THAT COMPLIES WITH UL
 300.
  
 3. A SINGLE STAIR IS DISPLAYED ON THE
 NORTH ELEVATION WHICH IS IN CLOSE
 PROXIMITY TO DOORS AND WINDOWS. DOES ANY
 OTHER EXITS EXIST FROM THE UPSTAIR
 APARTMENTS. IF NOT, A SINGLE MEANS OF
 EGRESS IS SHOWN WITH UNPROTECTED
 OPENINGS WITHIN 10 FEET OF THESE STAIRS.
 PLEASE ADVISE.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709