| Notes |
| Date |
Text |
| 2006-02-15 00:00:00 | 1. SEPARATE PLANS AND PERMITS REQUIRED | | | FOR HOOD, DUCT, AND SUPPRESSION SYSTEM. | | | | | | 2. PLANS MAKE REFERENCE TO A CO2 SYSTEM. | | | THE PLANS SHOULD REFERENCE A WET | | | CHEMICAL SYSTEM THAT COMPLIES WITH UL | | | 300. | | | | | | 3. A SINGLE STAIR IS DISPLAYED ON THE | | | NORTH ELEVATION WHICH IS IN CLOSE | | | PROXIMITY TO DOORS AND WINDOWS. DOES ANY | | | OTHER EXITS EXIST FROM THE UPSTAIR | | | APARTMENTS. IF NOT, A SINGLE MEANS OF | | | EGRESS IS SHOWN WITH UNPROTECTED | | | OPENINGS WITHIN 10 FEET OF THESE STAIRS. | | | PLEASE ADVISE. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 804-4709 |
|