| 2006-03-13 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | NOTE - NEW PLANS FROM A NEW DESIGN |
| | PROFESSIONAL |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1.) A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | THE NOC IS EXPIRED, OVER 90 DAYS WITHOUT |
| | COMMENCING WORK, FS713.13(2). |
| | |
| | 2.) IMPACT FEES MAY BE DUE (CHANGE OF |
| | USE).THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 |
| | |
| | THE RECEIPT WAS IN THE PACKAGE BUT THE |
| | PLANS WERE NOT STAMPED.WHEN |
| | RESUBMITTING, PLEASE BE SURE THAT BOTH |
| | ITEMS ARE INCLUDED. |
| | |
| | 3.)THE KITCHEN IS TO BE CONSTRUCTED SO |
| | THAT INDIVIDUALS WITH DISABILITIES CAN |
| | APPROACH, ENTER, AND EXIT THE AREA |
| | FBC11-4.1.1(3).DOOR IS TO COMPLY WITH |
| | FBC11-4.13. |
| | |
| | THIS WAS APPARENTLY ADDRESSED.THE |
| | ARCHITECT SENT A RESPONSE LETTER STATING |
| | "THE DEPARTMENT OF BUSINESS |
| | ADMINISTRATION INSISTED THAT THE KITCHEN |
| | IS CLOSED OFF BY A DOOR."WHAT DOES |
| | THIS MEAN? |
| | |
| | 4. - 7.)ADDRESSED. |
| | |
| | 8.)PROVIDE ELEVATIONS TO SHOW |
| | ACCESSIBLE ROUTE; APPEARS TO HAVE A STEP |
| | UP INTO THE BUILDING. |
| | |
| | ELEVATIONS NOT PROVIDED.SLOPES NOT |
| | PROVIDED. |
| | |
| | 9. - 12.)ADDRESSED. |
| | |
| | 13.)HOW WILL THE A/C BE ACCESSED?THE |
| | NOTE ON THE PLAN IS CONFUSING; STATES TO |
| | ACCESS THROUGH THE LAUNDRY ON 2ND FLOOR, |
| | BUT ISN'T THE LAUNDRY ON THE FIRST |
| | FLOOR? |
| | |
| | SHOW COMPLIANCE WITH FBC1007, ALL |
| | DETAILS - STAIR WIDTH, TREAD AND RISER |
| | DIMENSIONS FBC1007, ALL REQUIREMENTS OF |
| | FBC1006.2, HANDRAIL AND GUARDRAIL |
| | DIMENSIONS FBC1007 AND FBC1015, HANDRAIL |
| | AND GUARDRAIL DESIGN CRITERIA (FBC1608). |
| | |
| | THE DOOR IS AN 80IN DOOR, BUT THE |
| | DIMENSION FROM THE LANDING TO THE SECOND |
| | FLOOR SCALED IS APPROXIMATELY 72IN |
| | TOTAL, INCLUDING THE FLOOR/CEILING |
| | ASSEMBLY.ADDRESS. |
| | |
| | 14. - 15.)ADDRESSED. |
| | |
| | 16.)TWO MEANS OF EGRESS REQUIRED; |
| | TRAVEL DISTANCE EXCEEDS 50' FBC1025.1. |
| | |
| | THE TWO EXIT DOORS ARE LESS THAN HALF |
| | THE DIAGONAL DISTANCE APART, |
| | FBC1004.1.4.WHAT ARE THE TWO MEANS OF |
| | EGRESS FOR THE PERSON IN THE KITCHEN |
| | AREA TO THE REAR (SINKS)? |
| | |
| | 17.)THE HC RR DOOR BLOCKS THE EGRESS, |
| | FBC1012.1.4. |
| | |
| | IF THIS IS USED AS SECOND MEANS OF |
| | EGRESS FOR THE PERSON IN THE REAR |
| | KITCHEN AREA, THE COMMENT STILL APPLIES. |
| | |
| | NEW COMMENTS: |
| | |
| | 18.)SEE FBC1003.2.5 AND SHOW |
| | COMPLIANCE FOR THE MEZZANINE CEILING |
| | HEIGHT. |
| | |
| | 19.)SHOW FIRE RATING REQUIREMENT FOR |
| | THE DOORS WITHIN 10FT OF THE STAIRS, |
| | FBC705.1.2.PROVIDE FIRE RATING |
| | INFORMATION FOR THE SPECIFIC DOOR YOU |
| | ARE INSTALLING. |
| | |
| | 20.)SHOW ALL DETAILS AND DESIGN LOAD |
| | REQUIREMENTS FOR THE MEZZANINE.WAS THE |
| | ORIGINAL MEZZANINE PERMITTED LIKE THIS? |
| | |
| | 21.)PROVIDE AREA CALCULATIONS FOR THE |
| | SPACE.IT IS NOT CLEAR IF THE MEZZANINE |
| | WAS INCLUDED WHEN IMPACT FEES WERE PAID. |
| | |
| | 22.)PROVIDE WIND DESIGN CRITERIA |
| | REQUIRED BY FBC1606.1.7. |
| | |
| | 23.)THERE IS A BATHROOM SHOWN IN THE |
| | ADJACENT TENANT SPACE, PROP.EX.RR. |
| | PROPOSED EXISTING REST ROOM?WHAT DOES |
| | THIS MEAN? |
| | |
| | 24.)MECHANICAL EQUIPMENT IS SHOWN |
| | UNDER THE STAIRS, THE ONLY MEANS OF |
| | EGRESS FOR THE RESIDENTIAL OCCUPANTS ON |
| | THE SECOND FLOOR.THIS CREATES A FIRE |
| | HAZARD, SEE FBC1007 AND FBC1001.1.4. |
| | |
| | 25.)PREVIOUS PLANS MADE REFERENCE TO |
| | ACCESSING THE MEZZANINE FROM THE OTHER |
| | TENANT SPACE.WHAT HAPPENED TO THIS |
| | OPENING, NO LONGER SHOWN ON THE PLAN? |
| | |
| | 26.)OLD PLANS SHOWNO LANDING ON THE |
| | STAIRS, THIS PLAN SHOWS A LANDING. |
| | ADDRESS. |
| | |
| | 27.)SHOW REQUIRED TENANT/OCCUPANCY |
| | SEPARATION BETWEEN THE LAUNDROMAT AND |
| | THE RESTAURANT.DECLARE AN OCCUPANCY |
| | FOR THE RESTAURANT. |
| | |
| | 28.)SEE ATTACHED FS553.80(2)(B). |