| 2005-07-30 00:00:00 | PAUL SCHMITZ, PLUMBING & GAS PLANS |
| | EXAMINER561-805-6692 |
| | |
| | [email protected] |
| | PLUMBING GAS PLAN REVIEW FBC 2001 |
| | DENIED |
| | (1) ?3401.2.2 CHANGE OF OCCUPANCY |
| | ?3401.2.2.1 IF THE OCCUPANCY |
| | CLASSIFICATION OR OCCUPANCY |
| | SUBCLASSIFICATIONS OF ANY EXISTING |
| | BUILDING OR STRUCTURE IS CHANGED, THE |
| | BUILDING, ELECTRICAL, GAS, |
| | MECHANICAL AND PLUMBING SYSTEMS SHALL BE |
| | MADE TO CONFORM TO THE INTENT OF THE |
| | TECHNICAL CODES AS REQUIRED BY THE |
| | BUILDING OFFICIAL. |
| | ?3401.2.2.2 CHANGES IN THE OCCUPANCY |
| | OF A BUILDING NOW EXISTING OR |
| | HEREAFTER ERECTED SHALL NOT BE MADE |
| | UNTIL A REVISED CERTIFICATE OF |
| | OCCUPANCY HAS BEEN ISSUED BY THE |
| | BUILDING OFFICIAL CERTIFYING THAT THE |
| | FLOORS ARE SUITABLE FOR THE LOADS CHARACTERISTIC OF |
| | THE PROPOSED |
| | OCCUPANCY.SEE ?106. |
| | (2) CONTACT MS LYNN MASSON, WEST PALM |
| | BEACH ENVIROMENTAL COMPLIANCE |
| | FOR GREASE TRAP SIZING REQUIRMENTS. |
| | LOCAL ORDANCE. PHONE 561-822-2271 |
| | (3) CONTACT DEPT OF BUSINESS REGULATION |
| | HOTEL & RESTURANT DIVISION |
| | PROVIDE THEIR COMMENT SHEET AND TWO SETS |
| | OF STAMPED PLANS. |
| | (4) ?P403.2 SEPARATE FACILITIES. WHERE |
| | PLUMBING FIXTURES ARE REQUIRED, |
| | SEPARATE FACILITIES SHALL BE PROVIDED |
| | FOR EACH SEX. |
| | EXCEPTIONS: |
| | 2. SEPARATE EMPLOYEE FACILITIES SHALL |
| | NOT BE REQUIRED IN OCCUPANCIES IN |
| | WHICH 15 OR LESS PEOPLE ARE |
| | EMPLOYED. |
| | 3. SEPARATE FACILITIES SHALL NOT BE |
| | REQUIRED FOR FOOD SERVICE |
| | ESTABLISHMENTS WHICH SEAT 10 |
| | PERSONS OR LESS. |
| | ?P403.3 NUMBER OF OCCUPANTS OF EACH SEX. |
| | THE REQUIRED WATER CLOSETS, |
| | LAVATORIES, AND SHOWERS OR BATHTUBS |
| | SHALL BE DISTRIBUTED EQUALLY BETWEEN |
| | THE SEXES BASED ON THE PERCENTAGE OF |
| | EACH SEX ANTICIPATED IN THE OCCUPANT |
| | LOAD.THE OCCUPANT LOAD SHALL BE |
| | COMPOSED OF 50 PERCENT OF EACH SEX, |
| | UNLESS STATISTICAL DATA APPROVED BY THE |
| | CODE OFFICIAL INDICATE A DIFFERENT |
| | DISTRIBUTION OF THE SEXES.(SEE ALSO |
| | ?P403.1.1) |
| | (4) SHT A1.1 PLUMBING ISOMETRIC.DENIED |
| | KITCHEN AREA EQUIPMENT DRAIN TO GREASE |
| | WASTE SYSTEM. |
| | DISH WASHER DRAIN TO SANITARY SEWER. |
| | REST ROOM WASTE TO SANITARY SEWER. |
| | PROVIDE A WATER RISER ISOMETRIC SHOWING |
| | ALL FIXTURE CONNECTIONS. |
| | BACK FLOW PREVENTER REQUIRED AT METER. |
| | (5) PROVIDE A GAS PIPING ISOMETRIC |
| | SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | TYPE OF GAS, (LP OR NATURAL) |
| | BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | |
| | END OF COMMENTS |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |