Plan Review Notes
Plan Review Notes For Permit 05061669
Permit Number 05061669
Review Stop P
Sequence Number 1
Notes
Date Text
2005-07-30 00:00:00PAUL SCHMITZ, PLUMBING & GAS PLANS
 EXAMINER561-805-6692
  
 [email protected]
 PLUMBING GAS PLAN REVIEW FBC 2001
 DENIED
 (1) ?3401.2.2 CHANGE OF OCCUPANCY
 ?3401.2.2.1 IF THE OCCUPANCY
 CLASSIFICATION OR OCCUPANCY
 SUBCLASSIFICATIONS OF ANY EXISTING
 BUILDING OR STRUCTURE IS CHANGED, THE
 BUILDING, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS SHALL BE
 MADE TO CONFORM TO THE INTENT OF THE
 TECHNICAL CODES AS REQUIRED BY THE
 BUILDING OFFICIAL.
 ?3401.2.2.2 CHANGES IN THE OCCUPANCY
 OF A BUILDING NOW EXISTING OR
 HEREAFTER ERECTED SHALL NOT BE MADE
 UNTIL A REVISED CERTIFICATE OF
 OCCUPANCY HAS BEEN ISSUED BY THE
 BUILDING OFFICIAL CERTIFYING THAT THE
 FLOORS ARE SUITABLE FOR THE LOADS CHARACTERISTIC OF
 THE PROPOSED
 OCCUPANCY.SEE ?106.
 (2) CONTACT MS LYNN MASSON, WEST PALM
 BEACH ENVIROMENTAL COMPLIANCE
 FOR GREASE TRAP SIZING REQUIRMENTS.
 LOCAL ORDANCE. PHONE 561-822-2271
 (3) CONTACT DEPT OF BUSINESS REGULATION
 HOTEL & RESTURANT DIVISION
 PROVIDE THEIR COMMENT SHEET AND TWO SETS
 OF STAMPED PLANS.
 (4) ?P403.2 SEPARATE FACILITIES. WHERE
 PLUMBING FIXTURES ARE REQUIRED,
 SEPARATE FACILITIES SHALL BE PROVIDED
 FOR EACH SEX.
 EXCEPTIONS:
 2. SEPARATE EMPLOYEE FACILITIES SHALL
 NOT BE REQUIRED IN OCCUPANCIES IN
 WHICH 15 OR LESS PEOPLE ARE
 EMPLOYED.
 3. SEPARATE FACILITIES SHALL NOT BE
 REQUIRED FOR FOOD SERVICE
 ESTABLISHMENTS WHICH SEAT 10
 PERSONS OR LESS.
 ?P403.3 NUMBER OF OCCUPANTS OF EACH SEX.
 THE REQUIRED WATER CLOSETS,
 LAVATORIES, AND SHOWERS OR BATHTUBS
 SHALL BE DISTRIBUTED EQUALLY BETWEEN
 THE SEXES BASED ON THE PERCENTAGE OF
 EACH SEX ANTICIPATED IN THE OCCUPANT
 LOAD.THE OCCUPANT LOAD SHALL BE
 COMPOSED OF 50 PERCENT OF EACH SEX,
 UNLESS STATISTICAL DATA APPROVED BY THE
 CODE OFFICIAL INDICATE A DIFFERENT
 DISTRIBUTION OF THE SEXES.(SEE ALSO
 ?P403.1.1)
 (4) SHT A1.1 PLUMBING ISOMETRIC.DENIED
 KITCHEN AREA EQUIPMENT DRAIN TO GREASE
 WASTE SYSTEM.
 DISH WASHER DRAIN TO SANITARY SEWER.
 REST ROOM WASTE TO SANITARY SEWER.
 PROVIDE A WATER RISER ISOMETRIC SHOWING
 ALL FIXTURE CONNECTIONS.
 BACK FLOW PREVENTER REQUIRED AT METER.
 (5) PROVIDE A GAS PIPING ISOMETRIC
 SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 TYPE OF GAS, (LP OR NATURAL)
 BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
  
 END OF COMMENTS
  
  
  
  
  
  
  
  