2006-10-28 07:06:30PAUL SCHMITZ, PLUMBING & GAS PLANS
 EXAMINER561-805-6692
  
 [email protected]
 PLUMBING GAS PLAN REVIEW FBC 2001
  
 DENIED
  
 PREVIOUS NOTES FOR GAS NOT ADDRESSED
  
 WHEN RESUBMITTING.
 PLEASE INCLUDE A RESPONCE LETTER INDICATING HOW THE
 ITEMS WERE ADDRESSED, THIS WILL HELP TO EXPIDITE THE
 PLAN REVIEW.
  
 (1) SHT 2, GAS SYSTEM IS REQUIRED TO HAVE A EMERGENCY
 SHUT OFF VALVE FOR COOKING
 EQUIPMENT. A SHUTOFF VALVE IS REQUIRED UP STREAM STREAM
 OF THE EMERGENCY VALVE
 AND A UNION DOWN STREAM, SO VALVE CAN BE REPLACED OR
 REPAIRED.
  
 (2)SHT 2, PROVIDE A GAS PIPING ISOMETRICSUBMIT AN
 ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL CUT SECTIONS
 OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001 FUEL GAS CODE.
  
 (3) SHT 2,SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH NUMBER OF
 CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 (4) SHT 2, TYPE OF GAS, (LP OR NATURAL)
  
 (5) SHT 2, BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU
 LOAD ON THE SYSTEM. REFER TO THE FBC-2001 FUEL GAS CODE
 SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU 402(34).
  
 (6) SHT 2,SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
  
 (7) SHT 2,INDICATE THE DELIVERY PRESSURE (PSI) PER
 FBC-2001 FUEL GAS CODE SEC. 402.2. NATURAL GAS SPECIFY
 .5 PSI OR 2 PSI.
  
 (8) SHT 2, SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
  
 END OF COMMENTS