2005-07-13 00:00:00******DENIED******
  
 1) THE FLOOR PLAN MENTIONS 42 SEATS.
 PLEASE ILLUSTRATE HOW THIS WILL BE
 ACCOMPLISHED ON THE DRAWINGS.
  
 2) WHAT IS THE TOTAL OCCUPANCY LOAD FOR
 THE ENTIRE SPACE? IF IN EXCESS OF 50,
 THE DOOR SWINGS ARE INCORRECT, AND MUST
 SWING IN THE DIRECTION OF TRAVEL.
  
 3) PLANS INDICATE A SINGLE EXIT. DOES
 THIS SPACE MEET THE REQUIREMENTS TO
 ALLOW FOR THAT ARRANGEMENT?
  
 4) ELECTRICAL NOTES MENTION SMOKE
 DETECTORS. IF PROVIDED, PLEASE SHOW
 LOCATIONS ON THE PLANS.
  
 5) FIRE EXTINGUISHERS ARE REQUIRED.
 RATING TO BE 2A-10B,C IN SPACE, AND "K"
 TYPE IN THE KITCHEN.
  
 6) IF NOT ALREADY PROVIDED, A MINIMUM OF
 6" HIGH ADDRESS NUMBER IS REQUIRED ON
 THE BUILDING TO CONTRAST WITH
 BACKGROUND. PLEASE SHOW ON PLANS.
  
 7) COOKING THAT PRODUCES GREASE LADEN
 VAPOR REQUIRES A HOOD/SUPPRESSION
 SYSTEM. SEPARATE SHOP DRAWINGS AND
 PERMITS ARE REQUIRED FOR HOOD AND
 SUPPRESSION SYSTEM.
  
 8) IT WOULD APPEAR THAT THIS BUILDING
 MEETS THE DEFINITION OF MIXED OCCUPANCY.
 WHAT IS THE CURRENT OCCUPANCY OF THE
 SECOND FLOOR?
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951