| 2005-07-13 00:00:00 | ******DENIED****** |
| | |
| | 1) THE FLOOR PLAN MENTIONS 42 SEATS. |
| | PLEASE ILLUSTRATE HOW THIS WILL BE |
| | ACCOMPLISHED ON THE DRAWINGS. |
| | |
| | 2) WHAT IS THE TOTAL OCCUPANCY LOAD FOR |
| | THE ENTIRE SPACE? IF IN EXCESS OF 50, |
| | THE DOOR SWINGS ARE INCORRECT, AND MUST |
| | SWING IN THE DIRECTION OF TRAVEL. |
| | |
| | 3) PLANS INDICATE A SINGLE EXIT. DOES |
| | THIS SPACE MEET THE REQUIREMENTS TO |
| | ALLOW FOR THAT ARRANGEMENT? |
| | |
| | 4) ELECTRICAL NOTES MENTION SMOKE |
| | DETECTORS. IF PROVIDED, PLEASE SHOW |
| | LOCATIONS ON THE PLANS. |
| | |
| | 5) FIRE EXTINGUISHERS ARE REQUIRED. |
| | RATING TO BE 2A-10B,C IN SPACE, AND "K" |
| | TYPE IN THE KITCHEN. |
| | |
| | 6) IF NOT ALREADY PROVIDED, A MINIMUM OF |
| | 6" HIGH ADDRESS NUMBER IS REQUIRED ON |
| | THE BUILDING TO CONTRAST WITH |
| | BACKGROUND. PLEASE SHOW ON PLANS. |
| | |
| | 7) COOKING THAT PRODUCES GREASE LADEN |
| | VAPOR REQUIRES A HOOD/SUPPRESSION |
| | SYSTEM. SEPARATE SHOP DRAWINGS AND |
| | PERMITS ARE REQUIRED FOR HOOD AND |
| | SUPPRESSION SYSTEM. |
| | |
| | 8) IT WOULD APPEAR THAT THIS BUILDING |
| | MEETS THE DEFINITION OF MIXED OCCUPANCY. |
| | WHAT IS THE CURRENT OCCUPANCY OF THE |
| | SECOND FLOOR? |
| | |
| | |
| | MIKE WENNERGREN, A/CAPTAIN |
| | WPBFR(561) 805-6722 OR 835-2951 |