| Date |
Text |
| 2005-07-06 00:00:00 | ********* UNSAT ********* |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH PANEL |
| | SCHEDULE(S) TO BE SUBMITTED, |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE PLANS MENTIONS AHU TO |
| | BE ACCESIBLE THROUGH LAUNDRY MAT TENANT |
| | SPACE. THIS SHALL NOT BE PERMITTED. ALL |
| | ACCESS MUST BE FROM TENANT SPACE FOR |
| | REST. |
| | PLEASE SEE TENANT SEPARATION NOTES ETC |
| | FROM FIRE AND BLDG REVIEW. |
| | PLEASE SEE NEC FOR ACCESSIBILTY TO |
| | ELECTRICAL EQUIPMENT AND DISCONNECTING |
| | MEANS. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE CLARIFY NEW OR EXISTING |
| | REQUIRED SIGN CIRCUIT PER 600.5 |
| | |
| | 4)NOTE: PLEASE SHOW COND UNIT. |
| | DISCONNECT, GFI RECEPT ETC REQUIRED, |
| | 440.11,210.63 |
| | PLEASE ALSO SHOW MISSING LT/RECEPT FOR |
| | AHU,210.70,210.63 |
| | |
| | 5)NOTE: PLEASE CLARIFY NEW OR EXISTING |
| | SHOW WINDOW RECEPTS PER 210.62, LOADS TO |
| | BE SHOWN PER 220.12. |
| | |
| | 6)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| | FOR NEW LOADS AND EXSITNG LOADS. |
| | PLEASE INDICATE SIZE OF SERVICE, |
| | CONDUCTORS, GROUNDING, RISER ETC, NEW? |
| | EXISTING? |
| | 215.5,250.50,310.16,240.4,220 ETC. |
| | |
| | 7)NOTE: PLEASE SEE 210.8B3, WHICH |
| | REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT |
| | RECEPTACLES IN NONDWELLING-TYPE KITCHENS |
| | TO BE GFCI PROTECTED. THIS REQUIREMENT |
| | APPLIES TO EACH AND EVERY 15- AND |
| | 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, |
| | WHETHER OR NOT THE RECEPTACLE SERVES |
| | COUNTERTOP APPLIANCES. |
| | |
| | 8)NOTE: PLEASE SEE TITLE BLOCK MENTIONS |
| | ACI, ?? PLEASE CLARIFY? ARCH/ ENGINEERS |
| | ETC, CONTRACTOR LISTED ON APPLICATION |
| | MENTIONS SOMEONE ELSE. |
| | PLEASE SEE FAC 61G1-16.004, FAC |
| | 61G15-23.002, FS 481.219, AND 471.023 |
| | FOR POSSIBLE INFORMAITON REQUIRED. |
| | |
| | 9)NOTE: PLEASE SPECIFY OF THIS IS A |
| | "CHANGE IN OCCUPANCY". |
| | PLEASE SEE OTHER POSSIBE COMMENTS FROM |
| | OTHER TRADES WHCIH NAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | PLEASE REMOVE ALL OLD |