2005-08-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.) IMPACT FEES MAY BE DUE (CHANGE OF
 USE).THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.)THE KITCHEN IS TO BE CONSTRUCTED SO
 THAT INDIVIDUALS WITH DISABILITIES CAN
 APPROACH, ENTER, AND EXIT THE AREA
 FBC11-4.1.1(3).DOOR IS TO COMPLY WITH
 FBC11-4.13.
  
 4.) THE SINK HOT WATER PIPES (HC RR)
 SHALL BE INSULATED OR OTHERWISE
 CONFIGURED SO AS TO PROTECT AGAINST
 CONTACT, FBC11-4.24.6.
  
 5.)FIXED SEATING IS TO COMPLY WITH
 FBC11-5.1, FBC11-4.32.SHOW COMPLIANCE
 ON THE PLAN.
  
 6.)SHOW FRONT AND SIDE CLEAR FLOOR
 SPACE FOR THE WATER CLOSET,
 FBC11-4.16.2, FBC11 FIGURE 28.
  
 7.)DOOR HARDWARE TO COMPLY WITH
 11-4.13.9.
  
 8.)PROVIDE ELEVATIONS TO SHOW
 ACCESSIBLE ROUTE; APPEARS TO HAVE A STEP
 UP INTO THE BUILDING.
  
 9.)SHOW DOOR DIMENSIONS AND CLEARANCE.
  
 10.)NOTE THE DOOR CONSTRUCTION TYPE.
 IF IT IS WOOD, RODENT PROOFING REQUIRED
 FBC1205.1.1.
  
 11.)WHERE WILL THE EXHAUST DISCHARGE?
 WILL THEY GO THROUGH ANOTHER TENANT
 SPACE?
  
 12.)DECLARE AN OCCUPANCY FOR THE 2ND
 FLOOR.
  
 13.)HOW WILL THE A/C BE ACCESSED?THE
 NOTE ON THE PLAN IS CONFUSING; STATES TO
 ACCESS THROUGH THE LAUNDRY ON 2ND FLOOR,
 BUT ISN'T THE LAUNDRY ON THE FIRST
 FLOOR?
  
 14.)THE SEAL IS TO BE DATED
 FAC61G15-23.002.
  
 15.)DECLARE AN OCCUPANT LOAD.
  
 16.)TWO MEANS OF EGRESS REQUIRED;
 TRAVEL DISTANCE EXCEEDS 50' FBC1025.1.
  
 17.)THE HC RR DOOR BLOCKS THE EGRESS,
 FBC1012.1.4.
  
  
  
  