Plan Review Notes
Plan Review Notes For Permit 05061664
Permit Number 05061664
Review Stop M
Sequence Number 4
Notes
Date Text
2007-03-26 11:54:35MECHANICAL REVISION
 *** DENIED ***
 AS NOTED IN LAST REVIEW 3-16-07
 SEE MECHANICAL PLANS PAGE MEP.2.
  
 1) TWO SUPPLY AIR GRILLS IN BEDROOM ARE SHOWN AS RETURN
 GRILLS, PLEASE CORRECT.
  
 2) 24X12 RETURN AIR GRILL IS LOCATED IN THE BATHROOM,
 PLEASE RELOCATE TO BEDROOM.
  
 3) PLEASE SHOW CFM'S AT SUPPLY GRILLS.
  
 4) SEE 12" SUPPLY AIR DUCT TO 10X6 GRILL IN BATHROOM,
 PLEASE CORRECT.
  
 5)PLEASE OBSERVE THEIR ARE TWO 10" SUPPLY AIR DUCTS
 LEAVING THE AIR HANDLER AND ONLY ONE 12" RETURN AIR
 DUCT, WHICH MAY CAUSE A UNBALANCED AIR FLOW, PLEASE
 CORRECT OR SUBMIT MANUAL J CALCULATIONS TO SHOW THE AIR
 FLOW IS BALANCED, SEE 2004 FBC/R M1602.4 AND M1401.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.