| Plan Review Notes For Permit 05061664 |
| Permit Number |
05061664 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-03-26 11:54:35 | MECHANICAL REVISION | | | *** DENIED *** | | | AS NOTED IN LAST REVIEW 3-16-07 | | | SEE MECHANICAL PLANS PAGE MEP.2. | | | | | | 1) TWO SUPPLY AIR GRILLS IN BEDROOM ARE SHOWN AS RETURN | | | GRILLS, PLEASE CORRECT. | | | | | | 2) 24X12 RETURN AIR GRILL IS LOCATED IN THE BATHROOM, | | | PLEASE RELOCATE TO BEDROOM. | | | | | | 3) PLEASE SHOW CFM'S AT SUPPLY GRILLS. | | | | | | 4) SEE 12" SUPPLY AIR DUCT TO 10X6 GRILL IN BATHROOM, | | | PLEASE CORRECT. | | | | | | 5)PLEASE OBSERVE THEIR ARE TWO 10" SUPPLY AIR DUCTS | | | LEAVING THE AIR HANDLER AND ONLY ONE 12" RETURN AIR | | | DUCT, WHICH MAY CAUSE A UNBALANCED AIR FLOW, PLEASE | | | CORRECT OR SUBMIT MANUAL J CALCULATIONS TO SHOW THE AIR | | | FLOW IS BALANCED, SEE 2004 FBC/R M1602.4 AND M1401.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|