Plan Review Notes
Plan Review Notes For Permit 05061664
Permit Number 05061664
Review Stop E
Sequence Number 2
Notes
Date Text
2005-12-06 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} CAN'T FIND MANUFACTURERS
 SPECIFICATIONS FOR THE GENERATOR AND
 ATS.
  
 2} THE LOAD CALC SHOWN FOR PANEL "SB"(79
 AMPS) EXCEEDS THE SHOWN GENERATOR OUTPUT
 OF 59 AMPS. PLEASE CLARIFY.
  
 3} PLEASE CONFIRM THAT FPL IS PROVIDING
 GRC FOR THE SERVICE. TYPICALLY THIS
 WOULD BE PVC. ALSO 2-4/0 CONDUCTORS WILL
 NOT BE RUN WITH THE CABLE. THIS SECTION
 OF THE RISER MAY BE LEFT BLANK IF
 SUPPLIED BY FPL. THE DESIGNER ONLY NEEDS
 TO INDICATE THE SIZE OF THE MAIN BREAKER
 AND THE SERVICE CONDUCTORS FROM THAT
 POINT.
  
 4} THE 250 MCM CONDUCTORS FROM 400 AMP
 MAIN ARE IN VIOLATION OF 310.15(B)(6),
 THEY MUST BE A MINIMUM OF 500 MCM.
  
 5} THE TWO 4/0 "GROUNDS" SHOWN FROM THE
 METER/MAIN TO THE GUTTER ARE INCORRECT.
 ONE CONDUCTOR WOULD BE A NEUTRAL, AND
 THE OTHER A GROUND. THEY WOULD NOT BE
 THE SAME SIZE. SEE 250.122 FOR EQUIPMENT
 GROUND AND 310-15 FOR THE NEUTRAL SIZE.
  
 6} SHEET E.1 INDICATES PANELS "C,H,AND
 SB". SHEET E-2 RISER HAS DIFFERENT
 DESIGNATIONS, PLEASE CORRELATE.
  
 7} PANEL "H" IS SHOWN AS MLO (SCHEDULE).
 MUST HAVE THE MAIN INDICATED ON
 METER/MAIN.
  
 8} THE FEED FROM THE GUTTER TO THE 125
 AMP DISCONNECT MARKED (CH) DOES NOT HAVE
 A NEUTRAL. THE OTHER TWO DISCONNECTS DO
 NOT HAVE A GROUND.
  
 9} THE PANELS INTHE LAUNDRY ROOM DO NOT
 HAVE THE CLEARANCE REQUIREMENTS OF
 110.26.
  
 10} SEE 250.32(B)(1) FOR EQUIPMENT
 GROUND REQUIREMENT TO SEPERATE
 STRUCTURES. THE FEED TO THE CARRIAGE
 HOUSE MUST COMPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  