| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} CAN'T FIND MANUFACTURERS |
| | SPECIFICATIONS FOR THE GENERATOR AND |
| | ATS. |
| | |
| | 2} THE LOAD CALC SHOWN FOR PANEL "SB"(79 |
| | AMPS) EXCEEDS THE SHOWN GENERATOR OUTPUT |
| | OF 59 AMPS. PLEASE CLARIFY. |
| | |
| | 3} PLEASE CONFIRM THAT FPL IS PROVIDING |
| | GRC FOR THE SERVICE. TYPICALLY THIS |
| | WOULD BE PVC. ALSO 2-4/0 CONDUCTORS WILL |
| | NOT BE RUN WITH THE CABLE. THIS SECTION |
| | OF THE RISER MAY BE LEFT BLANK IF |
| | SUPPLIED BY FPL. THE DESIGNER ONLY NEEDS |
| | TO INDICATE THE SIZE OF THE MAIN BREAKER |
| | AND THE SERVICE CONDUCTORS FROM THAT |
| | POINT. |
| | |
| | 4} THE 250 MCM CONDUCTORS FROM 400 AMP |
| | MAIN ARE IN VIOLATION OF 310.15(B)(6), |
| | THEY MUST BE A MINIMUM OF 500 MCM. |
| | |
| | 5} THE TWO 4/0 "GROUNDS" SHOWN FROM THE |
| | METER/MAIN TO THE GUTTER ARE INCORRECT. |
| | ONE CONDUCTOR WOULD BE A NEUTRAL, AND |
| | THE OTHER A GROUND. THEY WOULD NOT BE |
| | THE SAME SIZE. SEE 250.122 FOR EQUIPMENT |
| | GROUND AND 310-15 FOR THE NEUTRAL SIZE. |
| | |
| | 6} SHEET E.1 INDICATES PANELS "C,H,AND |
| | SB". SHEET E-2 RISER HAS DIFFERENT |
| | DESIGNATIONS, PLEASE CORRELATE. |
| | |
| | 7} PANEL "H" IS SHOWN AS MLO (SCHEDULE). |
| | MUST HAVE THE MAIN INDICATED ON |
| | METER/MAIN. |
| | |
| | 8} THE FEED FROM THE GUTTER TO THE 125 |
| | AMP DISCONNECT MARKED (CH) DOES NOT HAVE |
| | A NEUTRAL. THE OTHER TWO DISCONNECTS DO |
| | NOT HAVE A GROUND. |
| | |
| | 9} THE PANELS INTHE LAUNDRY ROOM DO NOT |
| | HAVE THE CLEARANCE REQUIREMENTS OF |
| | 110.26. |
| | |
| | 10} SEE 250.32(B)(1) FOR EQUIPMENT |
| | GROUND REQUIREMENT TO SEPERATE |
| | STRUCTURES. THE FEED TO THE CARRIAGE |
| | HOUSE MUST COMPLY. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |