| 2005-07-21 00:00:00 | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PLEASE PROVIDE MANUFACTURERS |
| | SPECIFICATIONS FOR THE GENERATOR AND |
| | TRANSFER SWITCH SHOWN ON THE RISER |
| | DIAGRAM. |
| | |
| | 2} INDICATE THE SERVICE CONDUCTOR AND |
| | CONDUIT SIZE(S) FROM THE METER TO THE |
| | GUTTER. 215.5. |
| | |
| | 3} INDICATE TAP CONDUCTOR AND CONDUIT |
| | SIZES FROM THE GUTTER TO THE DISCONNECTS |
| | |
| | ON THE RISER. 215.5. |
| | |
| | 4} PLEASE SHOW A SITE PLAN LOCATING ALL |
| | SERVICE AND STANDBY EQUIPMENT. PLEASE |
| | NOTE IF THE 125 AMP PANEL ON THE RISER |
| | IS LOCATED AT OR ON THE CARRIAGE HOUSE |
| | IT MUST CONTAIN A MAIN BREAKER. A |
| | DISCONNECT MUST BE SUPPLIED PER 225.31. |
| | ALSO SEE 250.30 FOR GROUNDING |
| | REQUIREMENTS, NOT INDICATED ON THE |
| | RISER. |
| | |
| | 5} PLEASE GIVE A LOAD CALCULATION FOR |
| | THE STANDBY PANEL. SEE 702.5, ALL |
| | CIRCUITS HAVE LOADS, 5 ARE LISTED WITH |
| | NO LOADS ON THE SCHEDULE. |
| | |
| | 6} THE 3/0 CONDUCTORS RUN FROM THE 400 |
| | AMP DISCONNECT TO THE 400 AMP PANEL DO |
| | NOT COMPLY WITH 310.16 AMPERAGE |
| | REQUIREMENTS. |
| | |
| | 7} THE LAUNDRY CIRCUIT MUST COMPLY WITH |
| | 210.11(C)(2). 20 AMP #12 BC. |
| | |
| | 8) PLEASE SEE THE CONDUCTOR AND OCP SIZE |
| | |
| | FOR THE AHU AND A/C UNIT #1 ARE |
| | INCORRECT. 310.16. PLEASE VERIFY THE |
| | NAMEPLATE AT 17KVA ON AC#1. |
| | |
| | 7} THERE IS ONLY 1 SMALL APPLIANCE |
| | CIRCUIT LISTED ON THE PANEL SCHEDULE. |
| | SEE 210.11(C)(1). |
| | |
| | 8) THERE ARE 2 WATER HEATERS IN THE |
| | CALCULATION, ONLY ONE LISTED ON |
| | SCHEDULES. ALSO SEE THAT ONE LEG IS A |
| | #10 AND THE OTHER A #12 ON THE ONE |
| | SHOWN. |
| | |
| | 9} THE REFER AND SM APP CIRCUITS ON |
| | SCHED "SB" ARE SHOWN AS 2 POLE, PLEASE |
| | CORRECT. |
| | |
| | 10} LIST THE NEW BATH CIRCUITS PER |
| | 210.11(C)(3), INCLUDING CARRIAGE HOUSE, |
| | IN RESPECTIVE PANELS. |
| | |
| | IF THEERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/659-8026 |