Plan Review Notes
Plan Review Notes For Permit 05061622
Permit Number 05061622
Review Stop M
Sequence Number 1
Notes
Date Text
2005-07-06 00:00:00PROVISO:
 PLAN INDICATES "FREE RETURN" FOR BOTH
 AHU'S, PER 2001 FBC(M) 606.2.2 WHERE THE
 AGGREGATE AIR HAS THE DESIGN CAPACITY
 GREATER THAN 2,000 CFM, FAN SHUTDOWN
 WILL BE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.


Account Summary | Usage Policy | Privacy Policy