| Plan Review Notes For Permit 05061622 |
| Permit Number |
05061622 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-05 00:00:00 | ********** UNSAT ************ | | | | | | 1)NOTE; PLEASE SEE SHEET E-2 IS NOT | | | SIGNED WITH THE SAME SIGNATURE FROM | | | OTHER ELECTRICAL SHEETS. SIGNATURES ON | | | E-1 AND E-3 ARE RECOGNIZED AS SIGNATURE | | | FOR ENGINEER OF RECORD WHICH THIS OFFICE | | | IS FAMILAR WITH. | | | PLEASE SEE FS 471.025, ALL PLANS MUST BE | | | SIGNED, DATED AND SEALED BY THE ENGINEER | | | OF RECORD. | | | | | | 2)NOTE: PLEASE SEE EXISTING PANEL "A' ON | | | RISER INDICATES PANEL AS 225A AND PANEL | | | SCHEDULE SHOWS 200A? | | | PLEASE CORRELATE. | | | | | | PLEASE REMOVE ANY/OLD VOIDED SHEETS AND | | | ONLY INSERT NEW REVISED SHEETS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | ONE SET OF OLD VOIDED SHEETS SHOULD BE | | | SUBMITTED FOR REFERENCE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANYQUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|