2005-07-05 00:00:00********** UNSAT ************
  
 1)NOTE; PLEASE SEE SHEET E-2 IS NOT
 SIGNED WITH THE SAME SIGNATURE FROM
 OTHER ELECTRICAL SHEETS. SIGNATURES ON
 E-1 AND E-3 ARE RECOGNIZED AS SIGNATURE
 FOR ENGINEER OF RECORD WHICH THIS OFFICE
 IS FAMILAR WITH.
 PLEASE SEE FS 471.025, ALL PLANS MUST BE
 SIGNED, DATED AND SEALED BY THE ENGINEER
 OF RECORD.
  
 2)NOTE: PLEASE SEE EXISTING PANEL "A' ON
 RISER INDICATES PANEL AS 225A AND PANEL
 SCHEDULE SHOWS 200A?
 PLEASE CORRELATE.
  
 PLEASE REMOVE ANY/OLD VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANYQUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]