Plan Review Notes
Plan Review Notes For Permit 05061621
Permit Number 05061621
Review Stop B
Sequence Number 8
Notes
Date Text
2006-09-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)THE GOVERNING CODE AT THE TIME OF
 PERMIT APPLICATION WAS FBC2001, BUT THE
 PLANS STATE THAT IT WAS DESIGNED
 FBC2004.ASCE7-98 IS REFERENCED, WHICH
 IS THE CORRECT ENGINEERING STANDARD FOR
 THE 2001 CODE BUT NOT 2004 CODE.DESIGN
 INTENT IS NOT CLEAR.
  
 EITHER REVISE THE PLAN TO REFLECT
 FBC2001, OR SUBMIT A NEW PERMIT
 APPLICATION AND SUBMIT PLANS IN
 COMPLIANCE WITH FBC2004.
  
 2.)PROVIDE A CODE SUMMARY; GOVERNING
 CODE, BUILDING TYPE FBC6, BUILDING
 HEIGHT AND AREA FBC5, OCCUPANCY
 CLASSIFICATION FBC3, SPRINKLED OR
 UNSPRINKLED.
  
 3.)PROVIDE A SITE PLAN AND SHOW THE
 ACCESSIBLE ROUTE FBC11-4.1.2(1).
  
 4.)SEE FBC11-4.13.6 AND FBC11 FIGURE
 25 REGARDING MANEUVERING CLEARANCE, PULL
 SIDE, FOR DOOR 30, MASSAGE ROOM 3.
 PLANS SHOW AN OBSTRUCTION (COVERING OF
 PIPES); WHERE ARE THE PIPES ON THE WALL?
  
  
 5.)THE STAIR IS TO HAVE ACCESSIBLE
 HANDRAILS, FBC 11-4.9.4, PROVIDE A
 DETAIL.
  
 6.)PLEASE ADJUST VALUE, ADDITIONAL
 WORK SHOWN.
  
  
  