Plan Review Notes
Plan Review Notes For Permit 05061621
Permit Number 05061621
Review Stop E
Sequence Number 6
Notes
Date Text
2006-09-10 00:00:00** UNSAT **
  
 1) NOTE: PLEASE CORRLEATE ADDRESSING FOR
 PROJECT WITH NEW PLANS.
 PLEASE SEE THIS SCOPE OF WORK WAS
 PERMITTED UNDER THE ADDRESS OF 8100
 IBIS, AND REV COVER SHEET MENTIONS 8225
 AND THE PLANS INDICATE 8550. PLEASE
 CORRELATE AND REVISE.
  
 2) NOTE: PLEASE SEE A NOTE IS BEING
 PLACE ON PLANS FOR COMPLIANCE WITH 2004
 FBC 2004 13-415.1ABC.1.1. PLEASE SEE IF
 BRINGING THIS SPACE UP TO CODE FOR THIS,
 PLEASE PROVIDE DETAILS FOR SYSTEM BEING
 PROPOSED. NEED TO SHOW SYSTEM,
 SCHEDULING, OVER RIDES AND OVER RIDES
 LOCATION. PLEASE SEE LOCATION SHALL BE
 LOCATEDFOR INGRESS/EGRESS AREA AND
 BEING ABLE TO SEE THE LIGHTING WHICH IS
 BEING CONTROLLED. PLEASE SEE CONTROLS
 AND OVER RIDES FOR SEPARATE SPACES COULD
 NOT BE LOCATED. PLEASE SEEMAX TIMES FO
 OVER RIDING DEVICES MUST ALOS BE STATED.
 (TIMER TYPE 4HRS MAX, OCCUPANT SENSOR
 TYPE 30MINS MAX).
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND
 .1.3
 ** PLEASE SEE PREVIOUS NOTES WHICH
 REQUESTED SUBMITTIAL OFNEW ENGERGY
 CALCULATIONS BEIGN SIGNED, DATED AND
 SEALED BY NEW ARCHITECT OF RECORD.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  
  