Plan Review Notes
Plan Review Notes For Permit 05061621
Permit Number 05061621
Review Stop P
Sequence Number 3
Notes
Date Text
2006-01-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 A. FROM FIRST REVIEW: COMMENT NOT
 ADDRESSED.
  
 4. SHT A-1 NEW MENS AND WOMENS TOILET
 ROOMS, AND THE PLAYROOM TOILET ROOM
 SHALL BE ACCESSIBLE. SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19, & 11-4.22 AND "ALL
 SUBSECTIONS". SECTIONS 11-4.1.6(1)(B)
 AND 11-4.1.1(6).
  
 ***************NEW COMMENTS*************
 NEW SHEETS:
 1B. SHTS A-3 & P-1 SANT. RISER DIAGRAMS
 DO NOT REFLECT THE FLOOR PLAN. RISER FOR
 MASSAGE ROOM #3 DOES NOT SHOW THE FLOOR
 DRAIN. LAV SHALL CONNECT TO THE DRAIN
 LINE DOWNSTREAM OF THE FLOOR DRAIN NOT
 TO THE FLOOR DRAIN. - RISER DIAGRAM FOR
 MASSAGE ROOMS #'S 1 & 2 SHOW 3 TRAPS,
 BUT ONLY 2 SINKS SHOWN ON THE FLOOR
 PLAN. PLEASE CORRELATE RISERS AND FLOOR
 PLAN. SECTION 104.2.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  