| 2005-12-22 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FROM PREVIOUS TWO REVIEWS, NUMBERING |
| | REMAINS THE SAME FOR CONSISTENCY: |
| | |
| | 1.)PROVIDE PRODUCT APPROVALS FOR: |
| | |
| | DOORS TO BE REUSED (N/A) |
| | EXTERIOR DOOR |
| | STOREFRONT SYSTEM |
| | GLASS BLOCK (N/A) |
| | IMPACT PROTECTION |
| | ROOF TILE (N/A) |
| | ROOF MODIFIED (N/A) |
| | SOLARTUBE SKYLIGHTS (N/A) |
| | 7' SKYLIGHTS (N/A) |
| | |
| | (THIRD REVIEW) - MIAMIDADE NOAS FOR THE |
| | EXTERIOR DOOR WERE SUBMITTED AND APPEAR |
| | COMPLIANT, BUT FLORIDA STATE OR LOCAL |
| | PRODUCT APPROVAL IS ALSO REQUIRED, |
| | FAC9B72.WWW.FLORIDABUILDING.ORG |
| | |
| | IT APPEARS THAT THE DOORS TO BE REUSED |
| | WILL NOW BE "STORED FOR FUTURE USE" AND |
| | ARE NOT BEING REINSTALLED IN THIS |
| | PROJECT.IT APPEARS THAT THE GLASS |
| | BLOCK (EXTERIOR) AND THE SKYLIGHTS HAVE |
| | ALSO BEEN REMOVED FROM THE SCOPE OF |
| | WORK.IS THIS CORRECT? |
| | |
| | ONE ILLEGIBLE NOA FOR A NONIMPACT |
| | STOREFRONT SYSTEM WAS SUBMITTED.TWO |
| | LEGIBLE COPIES REQUIRED. |
| | |
| | IMPACT PROTECTION REQUIRED, FBC1606.1.4. |
| | REMOVABLE SHUTTERS MUST BE APPROVED BY |
| | THE BUILDING OFFICIAL.SEE ITEM #2 |
| | BELOW.THIS MUST BE ADDRESSED PRIOR TO |
| | PERMIT ISSUANCE. |
| | |
| | 2.)IS THERE A PLAN FOR INSTALLATION OF |
| | HURRICANE PROTECTIVE DEVICES FOR THIS |
| | BUILDING?IF YOU PROPOSE TO USE NON |
| | IMPACT GLASS ON A COMMERCIAL BUILDING, |
| | SUBMIT AN INSTALLATION PLAN FOR APPROVAL |
| | BY THE BUILDING OFFICIAL.SEE ATTACHED |
| | POLICY, ITEM #13. |
| | |
| | NOT ADDRESSED. |
| | |
| | 9.)IMPACT FEES REQUIRED.THE PLANS |
| | MUST BE STAMPED AND THE RECEIPT ATTACHED |
| | TO THE APPLICATION.233-5025 |
| | |
| | NOT ADDRESSED.NO CHANGES ARE SHOWN ON |
| | THE PLAN AND THE OLD SHEETS WERE NOT |
| | SUBMITTED.I BELIEVE THAT THE OLD |
| | SHEETS SHOWED A SMALL ADDITION, THIS |
| | PLAN APPARENTLY DOES NOT SHOW THE |
| | ADDITION.IS THIS CORRECT?WHEN |
| | RESUBMITTING, SHOW ALL CHANGES AND |
| | PROVIDE OLD SHEETS FOR REFERENCE. |
| | |
| | 10.)ENERGY CALCS REQUIRED FBC13. |
| | |
| | NOT ADDRESSED.THIS WAS AN ADDITION; IS |
| | THIS NOW ONLY AN ALTERATION? |
| | |
| | NEW COMMENT - |
| | |
| | 11.)SHOW MANEUVERING CLEARANCE, PULL |
| | SIDE, FOR DOORS 6 AND 12, FBC11 FIGURE |
| | 25. |
| | |
| | 12.)THE NOC IS EXPIRED, MORE THAN 90 |
| | DAYS WITHOUT COMMENCING WORK, |
| | FS713.13(2). |
| | |
| | ****WHEN RESUBMITTING, CLEARLY SHOW ALL |
| | CHANGES TO THE PLAN WITH CLOUDS AND |
| | SUBMIT THE OLD SHEETS FOR REFERENCE.A |
| | RESPONSE LETTER WOULD EXPEDITE PLAN |
| | REVIEW. *** |