Plan Review Notes For Permit 05061621
Permit Number 05061621
Review Stop B
Sequence Number 3
Notes
Date Text
2005-12-22 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FROM PREVIOUS TWO REVIEWS, NUMBERING
 REMAINS THE SAME FOR CONSISTENCY:
  
 1.)PROVIDE PRODUCT APPROVALS FOR:
  
 DOORS TO BE REUSED (N/A)
 EXTERIOR DOOR
 STOREFRONT SYSTEM
 GLASS BLOCK (N/A)
 IMPACT PROTECTION
 ROOF TILE (N/A)
 ROOF MODIFIED (N/A)
 SOLARTUBE SKYLIGHTS (N/A)
 7' SKYLIGHTS (N/A)
  
 (THIRD REVIEW) - MIAMIDADE NOAS FOR THE
 EXTERIOR DOOR WERE SUBMITTED AND APPEAR
 COMPLIANT, BUT FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL IS ALSO REQUIRED,
 FAC9B72.WWW.FLORIDABUILDING.ORG
  
 IT APPEARS THAT THE DOORS TO BE REUSED
 WILL NOW BE "STORED FOR FUTURE USE" AND
 ARE NOT BEING REINSTALLED IN THIS
 PROJECT.IT APPEARS THAT THE GLASS
 BLOCK (EXTERIOR) AND THE SKYLIGHTS HAVE
 ALSO BEEN REMOVED FROM THE SCOPE OF
 WORK.IS THIS CORRECT?
  
 ONE ILLEGIBLE NOA FOR A NONIMPACT
 STOREFRONT SYSTEM WAS SUBMITTED.TWO
 LEGIBLE COPIES REQUIRED.
  
 IMPACT PROTECTION REQUIRED, FBC1606.1.4.
 REMOVABLE SHUTTERS MUST BE APPROVED BY
 THE BUILDING OFFICIAL.SEE ITEM #2
 BELOW.THIS MUST BE ADDRESSED PRIOR TO
 PERMIT ISSUANCE.
  
 2.)IS THERE A PLAN FOR INSTALLATION OF
 HURRICANE PROTECTIVE DEVICES FOR THIS
 BUILDING?IF YOU PROPOSE TO USE NON
 IMPACT GLASS ON A COMMERCIAL BUILDING,
 SUBMIT AN INSTALLATION PLAN FOR APPROVAL
 BY THE BUILDING OFFICIAL.SEE ATTACHED
 POLICY, ITEM #13.
  
 NOT ADDRESSED.
  
 9.)IMPACT FEES REQUIRED.THE PLANS
 MUST BE STAMPED AND THE RECEIPT ATTACHED
 TO THE APPLICATION.233-5025
  
 NOT ADDRESSED.NO CHANGES ARE SHOWN ON
 THE PLAN AND THE OLD SHEETS WERE NOT
 SUBMITTED.I BELIEVE THAT THE OLD
 SHEETS SHOWED A SMALL ADDITION, THIS
 PLAN APPARENTLY DOES NOT SHOW THE
 ADDITION.IS THIS CORRECT?WHEN
 RESUBMITTING, SHOW ALL CHANGES AND
 PROVIDE OLD SHEETS FOR REFERENCE.
  
 10.)ENERGY CALCS REQUIRED FBC13.
  
 NOT ADDRESSED.THIS WAS AN ADDITION; IS
 THIS NOW ONLY AN ALTERATION?
  
 NEW COMMENT -
  
 11.)SHOW MANEUVERING CLEARANCE, PULL
 SIDE, FOR DOORS 6 AND 12, FBC11 FIGURE
 25.
  
 12.)THE NOC IS EXPIRED, MORE THAN 90
 DAYS WITHOUT COMMENCING WORK,
 FS713.13(2).
  
 ****WHEN RESUBMITTING, CLEARLY SHOW ALL
 CHANGES TO THE PLAN WITH CLOUDS AND
 SUBMIT THE OLD SHEETS FOR REFERENCE.A
 RESPONSE LETTER WOULD EXPEDITE PLAN
 REVIEW. ***