Plan Review Notes
Plan Review Notes For Permit 05061621
Permit Number 05061621
Review Stop E
Sequence Number 2
Notes
Date Text
2005-08-10 00:00:00************ UNSAT2ND REVIEW ********
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE SOME NEW COMMENTS FOR
 NEW ELECTRICAL INFORMATION SUBMITTED.
  
  
 1)NOTE: NOTE #1 OK.
 PLANS, SIGNED, DATED AND SEALED BY
 ARCHITECT.
  
 2)NOTE: NOTE #2 NO,
 PLEASE SEE RISER NOWS SHOWS ONE NEW
 ELECTRICAL SUB PANEL WITH PANEL
 SCHEDULE, HOWEVER NEW ELECTRICAL SUB
 PANEL DOES NOT INCLUDE OTHER CIRCUITS AS
 SHOWN ON PLANS.
 PLEASE SEE NO PANEL SCHEDULE FOR REVISED
 PANEL "A" WAS SUBMITTED.
 215.5
  
 3)NOTE: NOTE #3 NO, PLEASE SEE NEC
 220.3,220.10,220.11,220.13 ETC FOR LOAD
 CALCUALTIONS. PLEASE SEE GEN LT LOAD MAY
 NOT BE 1VA PER FT IN THIS OCCUPANCY.
 PLEASE ALSO SEE RECEPTS ETC ARE MISSING
 FROM LOAD CALCS.
 PLEASE BE SURE ALL CONTINUOUS LAODS ARE
 SHOWN AT 125% 215.3,230.42 ETC
  
 4)NOTE: NOTE #4 NO, PLEASE SEE THESE
 UNITS/ CIRCUITS FOR GEN UNITS AND
 LOCATIONS ARE STILL NOT SHOWN ON PLANS?
 PLEASE SHOW.
  
 5)NOTE: NOTE #5 NO, NO GFI PROTECTION IS
 INDICATED ON PLANS, PANEL SCHEDULE ETC.
 680.44.680.71
  
 NEW NOTES.
  
 6)NOTE: PLEASE CORRELATE CIRCUITING FOR
 HEATER ON NEW SUB PANEL WITH CONDCUTORS
 SHOWN ON RISER.
 215.5
  
 7)NOTE: PLEASE SEE LOAD CALCULATIONS
 INDICATE PANEL "A" AS 225A EXISITING AND
 RISER SHOWS THIS PANEL "A" AS 200A
 EXISTING?
 PLEASE CORRELATE.
 215.5
  
 8)NOTE: PLEASE SEE OTHER LOADS BESIDES
 NEW SPA LOADS ARE NOT SHOWN IN LOAD
 CALCUALTIONS?
 220,215.5
  
 9)NOTE: PLEASE SEE 680.43A FOR MIN GFI
 RECEPT REQUIRED.
  
 10)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 DESIGN PROFESSIONAL AND REPEAT COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
 PLEASE SEE ONE COPY OF ELECTRICAL PLANS
 ARE BEING RETAINED FOR FILE.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF ALL OLD/VOIDED SHEETS SHALL
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]