| 2005-08-10 00:00:00 | ************ UNSAT2ND REVIEW ******** |
| | |
| | PLEASE SEE SOME COMMENTS FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | PLEASE ALSO SEE SOME NEW COMMENTS FOR |
| | NEW ELECTRICAL INFORMATION SUBMITTED. |
| | |
| | |
| | 1)NOTE: NOTE #1 OK. |
| | PLANS, SIGNED, DATED AND SEALED BY |
| | ARCHITECT. |
| | |
| | 2)NOTE: NOTE #2 NO, |
| | PLEASE SEE RISER NOWS SHOWS ONE NEW |
| | ELECTRICAL SUB PANEL WITH PANEL |
| | SCHEDULE, HOWEVER NEW ELECTRICAL SUB |
| | PANEL DOES NOT INCLUDE OTHER CIRCUITS AS |
| | SHOWN ON PLANS. |
| | PLEASE SEE NO PANEL SCHEDULE FOR REVISED |
| | PANEL "A" WAS SUBMITTED. |
| | 215.5 |
| | |
| | 3)NOTE: NOTE #3 NO, PLEASE SEE NEC |
| | 220.3,220.10,220.11,220.13 ETC FOR LOAD |
| | CALCUALTIONS. PLEASE SEE GEN LT LOAD MAY |
| | NOT BE 1VA PER FT IN THIS OCCUPANCY. |
| | PLEASE ALSO SEE RECEPTS ETC ARE MISSING |
| | FROM LOAD CALCS. |
| | PLEASE BE SURE ALL CONTINUOUS LAODS ARE |
| | SHOWN AT 125% 215.3,230.42 ETC |
| | |
| | 4)NOTE: NOTE #4 NO, PLEASE SEE THESE |
| | UNITS/ CIRCUITS FOR GEN UNITS AND |
| | LOCATIONS ARE STILL NOT SHOWN ON PLANS? |
| | PLEASE SHOW. |
| | |
| | 5)NOTE: NOTE #5 NO, NO GFI PROTECTION IS |
| | INDICATED ON PLANS, PANEL SCHEDULE ETC. |
| | 680.44.680.71 |
| | |
| | NEW NOTES. |
| | |
| | 6)NOTE: PLEASE CORRELATE CIRCUITING FOR |
| | HEATER ON NEW SUB PANEL WITH CONDCUTORS |
| | SHOWN ON RISER. |
| | 215.5 |
| | |
| | 7)NOTE: PLEASE SEE LOAD CALCULATIONS |
| | INDICATE PANEL "A" AS 225A EXISITING AND |
| | RISER SHOWS THIS PANEL "A" AS 200A |
| | EXISTING? |
| | PLEASE CORRELATE. |
| | 215.5 |
| | |
| | 8)NOTE: PLEASE SEE OTHER LOADS BESIDES |
| | NEW SPA LOADS ARE NOT SHOWN IN LOAD |
| | CALCUALTIONS? |
| | 220,215.5 |
| | |
| | 9)NOTE: PLEASE SEE 680.43A FOR MIN GFI |
| | RECEPT REQUIRED. |
| | |
| | 10)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) ATTACHED WITH RESPECT TO |
| | DESIGN PROFESSIONAL AND REPEAT COMMENTS. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | PLEASE SEE ONE COPY OF ELECTRICAL PLANS |
| | ARE BEING RETAINED FOR FILE. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE COPY OF ALL OLD/VOIDED SHEETS SHALL |
| | BE SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SEE COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |