Plan Review Notes
Plan Review Notes For Permit 05061621
Permit Number 05061621
Review Stop P
Sequence Number 1
Notes
Date Text
2005-07-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. PLANS SHALL BE SIGNED BY THE
 ARCHITECT OF RECORD. STAMPED SIGNATRUES
 ARE NOT APPROVED. FAC 61G116.003 AND FS
 481.2055.
 2. SHT D1 INDICATES THE STEAM GENERATOR
 WILL BE REMOVED, BUT SHT A-1 INDICATES
 TWO STEAM ROOMS. PLEASE CLARIFY. SECTION
 104.2.1. - IF NEW STEAM GENERATORS ARE
 TO BE INSTALLED, DETAILS FOR THE NEW
 GENERATORS ARE REQUIRED. SHOW THE
 LOCATION OF THE STEAM GENERATORS, AS
 WELL AS THE INFORMATION ON THE EMERGENCY
 PAN, THE PAN DRAIN LINES, THE P/T VALVE
 DISCHARGE LINES ECT. SHOW ROUTING OF
 LINES AS WELL AS THE STEAM LINES TO THE
 STEAM ROOMS. INDICATE MATERIAL FOR ALL
 LINES AND EMERGENCY PAN. STEAM UNITS
 SHALL BE LISTED. SUBMIT MANUF.
 SPECIFICATION SHEETS.
 3. SHT A-1 SINK IN HALL #3 SHALL BE
 ACCESSIBLE. PLEASE PROVIDE A DETAIL
 SHOWING COMPLIANCE WITH 11-4.24 AND "ALL
 SUBSECTIONS"
 4. SHT A-1 NEW MENS AND WOMENS TOILET
 ROOMS, AND THE PLAYROOM TOILET ROOM
 SHALL BE ACCESSIBLE. SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19, & 11-4.22 AND "ALL
 SUBSECTIONS". SECTIONS 11-4.1.6(1)(B)
 AND 11-4.1.1(6).
 5. SHT A-3 SANT. RISER DIAGRAM FOR
 FLAYROOM TOILET ROOM, PIPE SIZE
 INDICATES 2" TO PICK UP TOILET. TABLE
 709.1 FOOTNOTE "D" STATES "TRAP SIZE
 SHALL BE CONSISTENT WITH THE FIXTURE
 OUTLET SIZE". PLEASE SUBMIT MANUF.
 SPECIFICATION FOR TOILET THAT INDICATES
 A 2" OUTLET FOR THE TOILET.
 6. SHT A-3 SANT. RISER DIAGRAM FOR NEW
 SPA AREAS. PLEASE INDICATE WHAT THE LINE
 TO THE RIGHT OF THE DRAIN LINE TO THE
 SPA FLOOR DRAIN LINE DOWNSTREAM OF THE
 FLOOR DRAINS IS DRAINING. SECTION
 104.2.1.
 7. PLEASE SUBMIT A PLUMBING FLOOR PLAN
 SHOWING ALL PIPING AND THE POINT OF
 CONNECTION FOR EACH RISER SHOWN ON SHT
 A-3.
 8. SHT A-3 SANT. RISER DIAGRAMS AND
 WATER RISER DIAGRAMS, SHOW ALL PIPE
 SIZES. SECTION 104.2.1.
 10. SHT A-2 PLUMBING NOTES:
 #1. PIPING SHALL BE PER TABLE 704.1.
 PIPING 2-1/2" OR SMALLER SHALL BE RUN
 WITH A MINIMUM SLOPE OF 1/4" PER FT.
 #8. INDICATE WHERE NEW SHOWER WILL BE
 INSTALLED. SECTION 104.2.1.
  
 REVIEW BY KEN STEVENS