Plan Review Notes
Plan Review Notes For Permit 05061621
Permit Number 05061621
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-01 00:00:00*********** UNSAT **************
  
 1)NOTE: PLEASE SEE ALL THREE SETS OF
 PLANS SUBMITTED CONTAIN A "STAMP" FOR
 THE SIGNATURE OF ARCHITECT. PLEASE SEE
 FS 481.221 WHICH REQUIRES THE ARCHITECT
 TO SIGN, DATE AND SEAL ALL PLANS. PLEASE
 SEE THIS SIGNATURE MUST BE AN ORIGINAL
 "WET" SIGNATURE. STAMPS ARE NOT
 ACCEPTABLE.
 PLEASE SEE ONE SET OF PLANS AHVE BEEN
 RETAINED FOR FILE. PLANS MAY BE TURNED
 OVER TO DBPR/ FLORIDA BOARD OF
 ARCHITECTS FOR POSSIBLE REVIEW.
 PLEASE SEE THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLEASE INCLUDE CIRCUITING ON
 PLANS FOR ALL NEW AND CORRELATE WITH A
 COMPLETE PANEL SCHEDULE TO BE SUBMITTED.
 215.5
  
 3)NOTE: PLEASE INCLUDE LOAD CALCAULTIOSN
 FOR NEW LOADS TO EXISTING LOADS. PLEASE
 INCLUDE SIZE, RATING ETC FOR PANEL. NO
 INFORMATION WAS SHOWN ON PLANS AND GIVEN
 AT THIS TIME.
  
 4)NOTE: PLEASE SEE NEW ELECTRICAL SPA,
 STEAM GEN ETC ARE INDICATED ON PANEL
 SCHEDULE, HOWEVER NONE OF THESE COULD BE
 LOCATED ON PLANS.??
 215.5
  
 5)NOTE: PLEASE INDICATE GFI PROTECTION
 FOR SPA CIRCUIT ETC PER 680.44,680.71
 ETC.
  
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY HAVE AN
 AFFECT ON ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  