| 2005-07-07 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | 1.)PROVIDE PRODUCT APPROVALS FOR: |
| | |
| | DOORS TO BE REUSED |
| | STOREFRONT SYSTEM |
| | GLASS BLOCK |
| | IMPACT PROTECTION |
| | ROOF TILE |
| | ROOF MODIFIED |
| | SOLARTUBE SKYLIGHTS |
| | 7' SKYLIGHTS |
| | |
| | 2.)IS THERE A PLAN FOR INSTALLATION OF |
| | HURRICANE PROTECTIVE DEVICES FOR THIS |
| | BUILDING?IF YOU PROPOSE TO USE NON |
| | IMPACT GLASS ON A COMMERCIAL BUILDING, |
| | SUBMIT AN INSTALLATION PLAN FOR APPROVAL |
| | BY THE BUILDING OFFICIAL.SEE ATTACHED |
| | POLICY, ITEM #13. |
| | |
| | 3.)SHOW HALLWAY WIDTH. |
| | |
| | 4.)THE PLAYROOM BATHROOM, NEW MEN'S |
| | TOILET AND NEW WOMEN'S TOILET ARE TO BE |
| | ACCESSIBLE, FBC11-4.1.6(1)(6).PROVIDE |
| | DETAILS FOR THE SINK, TOILET, TURNING |
| | SPACE, GRAB BARS. |
| | |
| | 5.)THE HALL#3 SINK IS TO BE COMPLIANT |
| | WITH |
| | |
| | 5.)SHOW COMPLIANCE WITH FBC11-4.13.7, |
| | FIG. 26 FOR VESTIBULE #1 AND #2 DOORS. |
| | |
| | 6.)SHOW MANEUVERIENG CLEARANCE FOR |
| | DOORS, FBC11-4.13.6, FIG 25 FOR THE |
| | FOLLOWING DOORS (PLEASE NOTE THAT OTHER |
| | DOORS ENCROACH THE CLEAR FLOOR SPACE): |
| | |
| | DOORS AT VEST #1 AND VEST #2 |
| | DOOR AT HALLWAY #1 AND #2 |
| | |
| | 7.)THE WINDOW BUCK IS TO PROVIDE FULL |
| | SUPPPORT (THE DETAIL ON A5 SHOWS THE |
| | WINDOW BEARING ON DRYWALL) UNLESS IT WAS |
| | TESTED THIS WAY, FBC1707.4.4.2.AS |
| | PRODUCT APPROVALS WERE NOT SUBMITTED FOR |
| | THE STOREFRONT I CANNOT DETERMINE |
| | WHETHER OR NOT THIS DETAIL IS CODE |
| | COMPLIANT. |
| | |
| | 8.) PROVIDE AREA CALCULATIONS ON THE |
| | PLAN (EXISTING, PROPOSED NEW, NEW |
| | TOTAL). |
| | |
| | 9.)IMPACT FEES REQUIRED.THE PLANS |
| | MUST BE STAMPED AND THE RECEIPT ATTACHED |
| | TO THE APPLICATION.233-5025 |
| | |
| | 10.)ENERGY CALCS REQUIRED FBC13. |
| | |