Plan Review Notes
Plan Review Notes For Permit 05061562
Permit Number 05061562
Review Stop E
Sequence Number 1
Notes
Date Text
2005-12-29 00:00:00PLANS ROUTED TO PLUMB.
2005-12-27 00:00:00********** UNSAT **********
  
  
 1)NOTE: PLEASE SEE FBC ADMINISTRATIVE
 CODE 106.3.4.3 WHICH REQUIRES PLANS TO
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR SAID
 PLANS/ DESIGN FOR SAID PLANS AND DESIGN.
  
 2)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS PER 2002 NEC
 210.12 WHICH REQUIRES ELECTRICAL OUTLETS
 IN BEDRMS TO BE PROTECTED. PLEASE KNOW
 THIS MEANS SD'S, RECEPTS, FANS, LTS ETC.
  
 3)NOTE: PLEASE SEE REDLINED PLANS FOR
 SOME RECEPTS MISSING PER 210.52.
  
 4)NOTE: PLEASE SEE 210.52C1 FOR MISSING
 COUNTERSPACE GFI(S) REQUIRED. SEE AREA
 OF DISHWASHER. SEE REDLINED PLANS.
  
 PLEASE REVMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF ANY OLD/VOIDED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]