| Date |
Text |
| 2006-04-18 00:00:00 | ********** UNSAT ********** |
| | |
| | PLEASE SEE THE FOLLOWING COMMENTS AS |
| | PLANS ARE COMING IN WITH A COMPLETE;Y |
| | DIFFERENT RISER FROM PREVIOUS PLANS |
| | SUBMITTED. |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE SEAL FROM |
| | ARCHITECT IS CLEAR AND VISABLE WITH ALL |
| | INFORMATION ON SIAD SEAL. PLEASE SEE |
| | SEAL IS UNREADABLE AT THIS TIME. |
| | FS 481.221,FAC 61G1-16.003 |
| | |
| | 2) NOTE: PLEASE CORRELATE RISER WITH NEW |
| | PANEL "B". (MISPRINT ON RISER. |
| | 215.5 |
| | |
| | 3) NOTE: PLEASE SEE A NEW PANEL IS BEING |
| | SHOWN FROM EXISTING PLANS WHICH NOW |
| | SHOWS PANELS BEING SUB-FED FROM THIS NEW |
| | PANEL, HOWEVER OCP CAN NOT VERIFIED AT |
| | THIS TIME AND NO PANEL SCHEDULE WAS |
| | SUBMITTED FOR THIS NEW PANEL. |
| | 215.5 |
| | PLEASE PROVIDE PANEL SCHEDULE AND |
| | INDICATE ALL NEW OCP FOR PANELS "B" AND |
| | PANEL "OLD EXISTING". |
| | PLEASE LABEL ALL PANELS. |
| | |
| | 4) NOTE: PLEASE SEE "OLD" PANEL IS SHOWN |
| | AS 50A ON RISER AND 60A ON PANEL |
| | SCHEDULE? |
| | 215.5 |
| | |
| | 5) NOTE: PLEASE SHOW THE LOCATION OF THE |
| | NEW SERVICE ON PLANS. METER/MAIN. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |