| Plan Review Notes For Permit 05061479 |
| Permit Number |
05061479 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2005-09-08 00:00:00 | ****** PROVISO/ REVISION ************ | | | | | | 1)NOTE: PLEASE SHOW THE SERVICE ENTRANCE | | | CONDUCOTR AND SIZEOF RISER. | | | 240.4,310.15B6,310.16,215.5 | | | | | | 2)NOTE: PLEASE CORRELATE FEEDERS ON | | | RISER TO EXSITNG PANEL "A" WITH FEEDERS | | | SHOWN ON NEW MCB PANEL. | | | PLEASE SEE ONE SHOWS #2 AND THE OTHER AS | | | #1. | | | | | | PLEASE SUBMIT THE ABOVE ALONG WITH ANY | | | OTHER REVISIONS, BEFORE ANY ROUGH | | | ELECTRICAL INSPECTIONS ARE CALLED IN. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | *** UNSAT *** | | | | | | PLEASE SEE PLANS NOT SEALED BY ARCHITECT | | | FS 481.221 |
|