| Plan Review Notes For Permit 05061479 |
| Permit Number |
05061479 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2005-08-12 00:00:00 | DENIED: | | | 1. FL. ENERGY CAL. IS CALLING FOR 18,600 | | | BTU'S & 12 SEER, PLANS SHOW 36,000 | | | BTU'S & 11 EER TO BE INSTALLED. FL. | | | ENERGY CAL. & PLANS NEED TO COINCIDE | | | WITH EACH OTHER. | | | 2. AUXILIARY DRAIN PAN SHOULD BE PLACED | | | BELOW A/H STAND AND HAVE A FLOAT SWITCH | | | INSTEAD OF AN AUXILIARY DRAIN LINE. | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | | TOM GORDON 805-6729 OR PATTY KRAUSS | | | 805-6719. | | | |
|