| Date |
Text |
| 2005-07-11 00:00:00 | ************ UNSAT *************** |
| | |
| | 1)NOTE: PELASE SEE ZONING COMMENTS |
| | PERTAINING TO MIN SET-BACKS REQUIRED. |
| | PLEASE SEE THIS WILL AFFECT ALL PLANS |
| | FOR ALL TRADES. |
| | |
| | 2)NOTE: PLEASE CORRELATE PANEL SCHEDULES |
| | AND RISER DIAGRAM. |
| | PLEASE SEE PANEL "B" SHOWS # 1 ON NEW |
| | MDP AND 1/0'S ON RISER. |
| | PLEASE SEE NEW PANEL "B" IS SHOWN AS |
| | PANEL "E" ON RISER. |
| | PLEASE ALSO SEE LABELING OF PANELS ON |
| | LOAD CALCULATIONS. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE PLANS ARE NOTED TO |
| | MENTION "UPGRADE EXISTING ELECTRICAL |
| | SERIVCE IF REQUIRED". |
| | PLEASE SEE THAT DETERMINATIONIS TO BE |
| | MADE AT THIS TIME. PLEASE INDICATE SIZE |
| | OF EXISTING METER-CAN,SEC'S IN RISER AND |
| | CONDUCTORS FROM METER TO NEW MCB PANEL. |
| | PLEASE SEE 310.16,310.15B6,240.4 ETC. |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE SEE LOAD CALCULATIONS ARE |
| | TO DONE PER 220.31B FOR ADDITIONS TO |
| | EXSITING. |
| | PLEASE ALSO SEE A/C LOADS MUST BE |
| | FIGURED ON LARGEST LOADS NOT ON SMALLER |
| | OF THE TWO BETWEEN AHU(HEAT) AND CU. |
| | PLEASE SEE A/C LOADS FOR PANEL "B" AND |
| | SERVICE WERE TAKEN FROM LOWER COOLING |
| | LOADS. PLEASE SEE 220.31B, 65% MAY NOT |
| | BE TAKEN FOR A/C LOADS. MUST BE 100%. |
| | |
| | 5)NOTE: PLEASE SEE FBC CHAPTER 34 FOR |
| | ADDTIONS TO EXSITING DWELLINGS. PLEASE |
| | SHOW ALL EXISTING OR NEW SD'S AND GFI'S |
| | TO MEET 2002 NEC AND NFPA-72 IN EXISTING |
| | DWELLING. |
| | |
| | 6)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 7)NOTE: PLEASE SEE ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE ARE TO BE GFI/GFI |
| | PROTECTED. 210.8A6 |
| | |
| | 8)NOTE: PLEASE SEE ONLY ONE SMALL |
| | APPLIANCE CIRCUIT INDICATED ON PANEL |
| | SCHEDULE. PLEASE SEE 210.52B1, 210.11C1 |
| | FOR A MIN OF TWO AND A MIN OF 1500VA PER |
| | CIRCUIT. |
| | |
| | 9)NOTE: PLEASE SEE MISSING REQUIRED |
| | DEDICATED BATH CIRCUIT PER 210.11C3, |
| | 210.52D. MUST BE 20A AND #12. |
| | |
| | 10)NOTE: PLEASE SEE 20A OCP ON #14 AWG |
| | FOR GDO ON NEW PANEL "B". |
| | 310.16,240.4 |
| | |
| | 11)NOTE:PLEASE SEE BOTH PANELS REFERENCE |
| | ARC FAULT PROTECTION FOR RECEPTS ONLY. |
| | PLEASE SEE 2002 210.12 FOR PROTECTION OF |
| | ALL OUTLETS IN BEDROOMS. LTS, FANS, SD'S |
| | RECEPTS ETC. |
| | PLEASE SEE NEXT NOTE ALSO. |
| | |
| | 12)NOTE: PLEASE SEE SD'S ARE NOTED ON |
| | PLANS HOWEVER THESE ARE NOT ON PLANS. |
| | PLEASE SEE PREVIOUS NOTE FOR REQUIRED |
| | SD'S AND PLEASE SEE 210.12 FOR ARC FAULT |
| | PROTECTION. IF WIRED AS NOTED, THIS |
| | WOULD PLACE ARC FAULT PROTECTION FOR |
| | OTHER CIRCUITS. |
| | |
| | 13)NOTE:PLEASE SEE PLANS ARE NOTED TO 99 |
| | NEC. WE ARE UNDER THE 2002 NEC WHICH WAS |
| | ADOPTED ON JULY 1ST, 2003 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE BE AWARE OF ANY COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. (ZONING). |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |