| Plan Review Notes For Permit 05061473 |
| Permit Number |
05061473 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-16 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 BUILDING | | | | | | | | | 1. LIST OF DRAWINGS INDICATE SHEETS LP-1 | | | AND LP-2. THESE SHEETS HAVE NOT BEEN | | | SUBMITTED. PLEASE CLARIFY SECTION | | | 104.2.1. | | | 2. SHT A2 SUBMIT CALCULATIONS FOR | | | PRIMARY AND SECONDARY ROOF DRAINS. SHOW | | | TOTAL AREA OF ROOF, AND INDICATE AREA | | | DRAIND BY EACH DOWNSPOUT. SHOW 1/2 AREA | | | OF VERTICAL WALLS INCLUDING PARAPETS | | | ADDED TO CALCULATIONS. | | | 3. ROOF DOWNSPOUTS SHALL DISCHARGE AT | | | LEAST 1 FOOT AWAY FROM THE STRUCTURE | | | SIDEWALL. SECTION 1503.4.4. PLEASE | | | INDICATE HOW THIS WILL BE ACCOMPLISHED. | | | 4. SHT MP1 CLEANOUTS ON THE TWO UPSTREAM | | | DUILDING DRAIN LINSE DO NOT COMPLY WITH | | | SECTION 706.3 AND DO NOT GUIDE THE WASTE | | | IN THE DIRECTION OF FLOW. - SUGGEST ALL | | | BUILDING DRAIN LINE HAVE A TWO WAY | | | CLEANOUT OUTSIDE THE BUILDING FOR EASY | | | ACCESS FOR SERVICE. SEE RED LINE | | | CORRECTIONS ON ONE SET OF PLANS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|