Plan Review Notes
Plan Review Notes For Permit 05061473
Permit Number 05061473
Review Stop P
Sequence Number 1
Notes
Date Text
2005-07-16 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 BUILDING
  
  
 1. LIST OF DRAWINGS INDICATE SHEETS LP-1
 AND LP-2. THESE SHEETS HAVE NOT BEEN
 SUBMITTED. PLEASE CLARIFY SECTION
 104.2.1.
 2. SHT A2 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 TOTAL AREA OF ROOF, AND INDICATE AREA
 DRAIND BY EACH DOWNSPOUT. SHOW 1/2 AREA
 OF VERTICAL WALLS INCLUDING PARAPETS
 ADDED TO CALCULATIONS.
 3. ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT AWAY FROM THE STRUCTURE
 SIDEWALL. SECTION 1503.4.4. PLEASE
 INDICATE HOW THIS WILL BE ACCOMPLISHED.
 4. SHT MP1 CLEANOUTS ON THE TWO UPSTREAM
 DUILDING DRAIN LINSE DO NOT COMPLY WITH
 SECTION 706.3 AND DO NOT GUIDE THE WASTE
 IN THE DIRECTION OF FLOW. - SUGGEST ALL
 BUILDING DRAIN LINE HAVE A TWO WAY
 CLEANOUT OUTSIDE THE BUILDING FOR EASY
 ACCESS FOR SERVICE. SEE RED LINE
 CORRECTIONS ON ONE SET OF PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]