| Plan Review Notes For Permit 05061473 |
| Permit Number |
05061473 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-21 00:00:00 | *************PLAN CHECK ONLY************ | | | | | | NO MECHANICAL PLANS OR CONTRACTOR | | | INDICATED.PLANS APPEAR TO BE FOR THE | | | "SHELL" BUILDING ONLY. | | | | | | 1.PLEASE PROVIDE ENERGY CALCULATIONS | | | IN ACCORDANCE WITH 2001 FBC CHATPER 13 | | | SUB-CHAPTER 4. | | | | | | 2.PLAN SHEET S-2 & MP-1 INDICATE | | | MECHANICAL EQUIPMENT LOCATED ON THE | | | ROOF.ROOF CURBS & STANDS SHALL COMPLY | | | WITH 2001 FBC 1511.7 FOR HEIGHT | | | REQUIREMENT ABOVE THE FINISHED ROOF. | | | | | | 3.PER 2001 FBC(M)306.5, EQUIPMENT | | | LOCATED ON THE ROOF AT A HEIGHT GREATER | | | THAN 16 FT, SHALL HAVE A PERMANENT MEANS | | | OF ACCESS.SUCH ACCESS SHALL NOT | | | REQUIRE CLIMBING OVER OBSTRUCTIONS | | | GREATER THAN 30" (PARAPET WALL). | | | | | | PLEASE INDICATE IF INTERIOR BUILDOUT | | | WILL BE UNDER A SEPARATE PERMIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|