2005-07-21 00:00:00*************PLAN CHECK ONLY************
  
 NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED.PLANS APPEAR TO BE FOR THE
 "SHELL" BUILDING ONLY.
  
 1.PLEASE PROVIDE ENERGY CALCULATIONS
 IN ACCORDANCE WITH 2001 FBC CHATPER 13
 SUB-CHAPTER 4.
  
 2.PLAN SHEET S-2 & MP-1 INDICATE
 MECHANICAL EQUIPMENT LOCATED ON THE
 ROOF.ROOF CURBS & STANDS SHALL COMPLY
 WITH 2001 FBC 1511.7 FOR HEIGHT
 REQUIREMENT ABOVE THE FINISHED ROOF.
  
 3.PER 2001 FBC(M)306.5, EQUIPMENT
 LOCATED ON THE ROOF AT A HEIGHT GREATER
 THAN 16 FT, SHALL HAVE A PERMANENT MEANS
 OF ACCESS.SUCH ACCESS SHALL NOT
 REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30" (PARAPET WALL).
  
 PLEASE INDICATE IF INTERIOR BUILDOUT
 WILL BE UNDER A SEPARATE PERMIT.
  