| 2005-07-06 00:00:00 | ************* UNSAT ************** |
| | |
| | PLANS SUBMITTED FOR "PLAN REVIEW |
| | ONLY" AND NOT FOR PERMIT. |
| | |
| | 1)NOTE: PLEASE SEE SHEETS PD1, PD2,PM, |
| | WS-1 ARE ALL SEALED PHOTOCOPIES AND DO |
| | NOT CONTIAN THE ORIGINAL SIGNATURE BY |
| | SAID ENGINEER OF RECORD. PLEASE ALSO SEE |
| | |
| | WS-2 AND WS3 ARE ONNLY PHOTOCOPIES AND |
| | DO NOT CONATIN ORIGINAL SIGNATURE OR |
| | SEAL. ONCE AGAIN, THESE ARE ALSO |
| | PHOTOCOPIES OF SIGNED PLANS. |
| | PLEASE SEE THIS COMMENT IS MADE WHETHER |
| | OR NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 2) NOTE: PLEASE SEE PLANS FORSITE |
| | LIGHTING SHALL BEAR THE PRINTED NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | PLANS/ DESIGN FBC 104.2.1 |
| | PLEASE INCLUDE CIRCUITING AND CORRELATE |
| | WITH PANEL SCHEDULE. |
| | |
| | 3)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | FOR WIND LOADING OF SITE LIGHTING POLES |
| | AND FIXTURES PER FBC 140 MPH. |
| | |
| | 4)NOTE: PLEASE CLARIFY ROOF-TOP GFI FOR |
| | A/C EQUIPMENT. 210.63 |
| | |
| | 5)NOTE: PLEASE SEE LOAD CALCULATIONS |
| | SHALL INDICATE SQ FT ETCPLEASE SHOE |
| | CALCS AND HOW LOADS WERE DERIVED. |
| | PER 220,10,220.11,220.13, ETC. |
| | PLEASE SEE ALL CONTINUOUS LOADS ARE TO |
| | BE SHOWN 125% ALONG WITH LARGETS MOTOR |
| | LOADS. |
| | 215.3,230.42 ETC. |
| | |
| | 6)NOTE: PLEASE INDICATE CONDUCTORS FROM |
| | GUTTER TO METER(S). |
| | PLEASE INCLUDE SIZING FOR GUTTER BASED |
| | ON SEC'S. |
| | 366,215.5 |
| | |
| | 7)NOTE: PLEASE SEE RISER SEEMS TO |
| | INDICATE PANELS FOR TENANTS AS FUTURE, |
| | HOWEVER PANEL SCHEDULES AND PLANS SEEM |
| | TO INDICATE BEING INSTALLED AT THIS |
| | TIME? |
| | PLEASE ONLY SHOW CONDUITS STUBBED IN |
| | TENANT SPACES IF IN SCOPE OF WORK OR?? |
| | 215.5 |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT ANY NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |