| Plan Review Notes For Permit 05061441 |
| Permit Number |
05061441 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-11 00:00:00 | ---------------PROVISO------------------ | | | GENERATOR EXHAUST TERMINATION TO | | | TERMINATE MIN. 10' FROM OPENINGS INTO | | | BUILDING STRUCTURE (DOORS, WINDOWS) AND | | | IN COMPLIANCE WITH FBC,M 804.3 | | | | | | RONALD J REGUEIRO | | | 561-805-6734 | | | [email protected] |
|