| 2007-10-11 10:34:24 | REVIEW #: 2 |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC |
| | CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. AS STATED IN PREVIOUS COMMENT, THE FLA/COM ENERGY |
| | CALCULATIONS SHALL BE REVISED USING THE PROGRAM WHICH |
| | WAS IN EFFECT AT THE TIME OF PERMIT APPLICATION. MIXING |
| | OF CODES IS PROHIBITED. PLEASE SUBMIT REVISED |
| | CALCULATIONS USING FORM 400A-2001. |
| | NOTE: BE SURE TO CHECK THE INPUT DATA REPORT AND VERIFY |
| | COMPLIANCE AND ACCURACY OF ALL ELEMENTS LISTED IN THE |
| | REPORT. EXAMPLE: LIGHTING DATA INDICATES ONE 2000 WATT |
| | FIXTURE FOR ALLL INTERIOR LIGHTING. INFORMATION IN THE |
| | REPORT SHALL ACCURATELY REFLECT THE INFORMATION SHOWN |
| | ON PLANS IN ACCORDANCE WITH FBC 13-400.3.ABCD.1. |
| | |
| | 2. OK |
| | |
| | 3. NOTES AND PLANS REGARDING CONDENSATE DISPOSAL |
| | INDICATE TRAPS AT EACH AHU AS WELL AS UNDERGROUND DRAIN |
| | LINES CREATING A DOUBLE TRAP. CONDENSATE DRAINS SHALL |
| | BE TRAPPED AS REQUIRED BY THE |
| | EQUIPMENT OR APPLIANCE MANUFACTURER. PLEASE CONFIRM |
| | THAT THIS METHOD IS IN COMPLIANCE WIITH MANUFACTURER'S |
| | INSTRUCTIONS AND PROVIDE SUPPORTING DOCUMENTATION. |
| | |
| | 4. A "REVISED" SITE PLAN HAS BEEN PROVIDED. HOWEVER, |
| | THE FOLLOWING DEFICIENCIES EXIST: |
| | A. ONLY ONE COPY WAS PROVIDED. AT LEAST TWO COPIES ARE |
| | REQUIRED FOR ALL PLANS AND SPECIFICATIONS PER FBC |
| | 104.2.1. |
| | B. PLANS HAVE BEEN PHOTOCOPIED. PLANS SHALL CONTAIN THE |
| | ORIGINAL SEAL, SIGNATURE AND DATE OF THE DESIGNER OF |
| | RECORD IN ACCORDANCE WITH FBC 104.2.2 AND FS 471. C. |
| | SIGNED AND SEALED PLANS SHALL NOT BE ALTERED BY HAND OR |
| | USE OF CORRECTION FLUID (SUCH AS WHITE-OUT). PROVIDE |
| | TWO SETS OF THE REVISED SITE PLANS WITH ALL INFORMATION |
| | LISTED ABOVE ADDRESSED. |
| | |