| 2005-12-09 00:00:00 | **** PLANS REDLINED **** | | | | | | ** PLEASE INFORM ENGINEER OF NOTE AND | | | REVISE WHEN MAKING ANY OTHER CHANGES TO | | | PLANS AND WHEN SUBMITTED FOR PLAN | | | REVIEW. | | | | | | | | | 1)NOTE: PLEASE SEE THE PREVIOUS NOTE#4 | | | WAS FOR THE "EQUIPMENT GROUNDING | | | CONDUCTOR", HOWEVER CHANGES TO THE | | | "GROUNDING ELECTRODE CONDUCTOR" WERE | | | MADE INSTEAD. | | | PLEASE SEE 250.66, THE MIN SIZE FOR THE | | | GEC IS 1/0. | | | PLEASE SEE 250.6.250.24 FOR PERMITTED | | | ATTACHMENT LOCATIONS. | | | | | | PLEASE SEE THE "EQUIPMENT GROUNDING | | | CONDUCTORS" FROM THE FIRST MEANS OF | | | DISCONNECT TO PANEL ARE OK. | | | | | | | | | PLEASE MAKE ANY CHANGES TO THE GEC FOR | | | BOTH SERVICES WITH ANY OTHER REVISIONS. | | | | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|