| 2005-07-07 00:00:00 | ************* UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEEBLDH #2 APPEARS TO |
| | HAVE OFFICES. PLEASE PROVIDE SIGN |
| | CIRCUIT PER 600.5 |
| | |
| | 2)NOTE: PLEASE CLARIFY OF INDEED THESE |
| | WILL BE OFFICES, WILL THERE BE ANY A/C |
| | UNITS? IF SO PLEASE SHOW. |
| | THIS IS ONLY A NOTE: |
| | |
| | 3)NOTE: PLEASE SEE ROOM AT LOCATION OF |
| | PANEL "J" IS LABELED AS STORAGE ON |
| | A-PLANS. PLEASE ADJUST RM DESIGNATION AS |
| | ELECTRICAL RM/ NO STORAGE ON PLANS AT |
| | BOTH LOCATION. 110.26,408.7 |
| | |
| | 4)NOTE: PLEASE SEE 250.6,250.24. |
| | EQUIPMENT GROUNDING CONDUCTORS SHALL NOT |
| | BE INSTALLED UNTIL AFTER THE FIRST MEANS |
| | OF DISCONNECT. PLEASE SEE RISER SHOWS A |
| | 1/0 AS AN EQUIPMENT GROUNDING CONDUCTOR |
| | FROM GUTTER TO METER AND METER TO FIRST |
| | MEANS OF DISC. |
| | |
| | 5)NOTE: PLEASE SEE PLUMB REVIEW NOTES |
| | FOR ENGINEER'S SIGNATURE OF RECORD ON |
| | PLUMB SHEETS. |
| | |
| | PLEASE SEE ANY OTHER POSSIBLE COMMENTS |
| | FROM OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEWL. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| 2005-07-06 00:00:00 | IN ELEC FOR REVIEW. |