| Plan Review Notes For Permit 05061382 |
| Permit Number |
05061382 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-06-29 00:00:00 | ****** PROVISO / REVISION ******* | | | | | | 1)NOTE: PLEASE SEE E-2 SHOWS MDP NEXT TO | | | DISCONNECT FOR FELLOWSHIP HALL PANEL. | | | PLEASE SEE RISER INDICATES FELLOWSHIP | | | HALL PANEL AS BEING MDP? THIS APPEARS TO | | | BE A MISPRINT OF MSB IN MECH RM. | | | | | | 2)NOTE: PLEASE SEE 700.12E FOR | | | CIRCUITING OF EM/EXT LTS. PLEASE SEE | | | EXCEPTION, FOR A LOCK-OFF TYPE BRKR | | | REQUIRED SINCE EXISITNG WIRING. | | | | | | 3)NOTE: PLEASE PLACE NOTE ON RISER | | | "NO OTHER BRKRS MAY BE INSTALLED IN MSB" | | | PLEASE SEE 230.70. | | | PLEASE SEE A MCB SHOULD BE INSTALLED IN | | | MSB IF POSSIBLE ALLEAVIATE MORE THAN 6 | | | POSSIBLE MAINS. THIS IS ONLY A NOTE | | | SINCE THIS IS A EXISTING CONDITION AND | | | SERVICE IS NOT BEING ALTERED. | | | | | | PLEASE SUBMIT THE ABOVE CHANGES BEFORE | | | INSPECTIONS ARE CALLED IN. IF THERE ARE | | | ANY QUESTIONS, PLEASE DO NOT HESITATE IN | | | CONTACTING ME. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|