Plan Review Notes
Plan Review Notes For Permit 05061381
Permit Number 05061381
Review Stop P
Sequence Number 2
Notes
Date Text
2006-01-31 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 A. FROM PREVIOUS REVIEW. COMMENT NUMBER
 WILL STAY THE SAME AS FIRST REVIEW:
  
 4. SHTS A1.2, A1.3, & A1.4 REFERENCE
 EQUIPMENT LAYOUT PLAN, AND EQUIPMENT
 SCHEDULES. IF THE EQUIPMENT IN THE
 RESTURANT IS BEING ALTERED, MOVED,
 ADDED, OR DELETED, PLANS SHALL BE ROUTED
 TO DBPR DIVISION OF HOTELS & RESTURANTS
 FOR REVIEW. PLANS WILL BE STAMPED BY
 DBPR REVIEWERS AND 2 PAGE "WORKSHEETS"
 WILL BE ATTACHED TO EACH SET OF PLANS
 RESUBMITTED TO CITY OF WPB FOR REVIEW.
 SECTION 101.4.7 - PLEASE INDICATE IF THE
 FOOD PREP/KITCHEN AREA WILL BE CHANGED
 OR IF ALL EQUIPMENT WILL BE REINSTALLED
 IN THE SAME LOCATION. SECTION 104.2.1. -
 ATTACH THE STAMPED SHEET FROM DBPR AND
 THE TWO SECTION "SPECIFICATION
 WORKSHEETS" TO EACH SET OF PLANS
 SUBMITTED FOR APPROVAL.
 5. SHT A8.3 RESTROOM ELEVATIONS. SHOW
 THE FOLLOWING:
 (FOR THE URINAL)
 C. 11-4.18.3 CLEAR FLOOR SPACE - NOT
 SHOWN.
 (FOR THE LAVS)
 E. 11-4.19.3 CLEAR FLOOR SPACE - LAV IN
 MEN'S TOILET ROOM SHALL BE ACCESSIBLE
 ALSO FOR USE BY PERSONS USING ACCESSIBLE
 URINAL. - NOT SHOWN.
 F. 11-4.19.5 FAUCETS - NOT ADDRESSED.
 6. SHT A1.2 TURNING AREA REQUIRED IN
 SECTION 11-4.22.3 SHALL BE IN THE TOILET
 ROOM, NOT THE STALL. - NOT ADDRESSED.
 9. SHT P1.1 NEW GREASE INTECEPTORS ARE
 INDICATED. PLEASE CONTACT LYNN MASSON
 ENVIRONMENTAL COMPLIANCE FOR SIZING.
 PLEASE CONTACT HER AT (561) 822-2271,
 FAX (561) 822-2279, OR E-MAIL
 [email protected]. SUBMIT DETERMINATION
 SHEET WITH EACH SET OF PLANS WHEN
 RESUBMITTING. WASTE ORD. #3434. PLEASE
 SUBMIT APPROVAL SHEET FROM ENVIRONMENTAL
 COMPLIANCE MANAGER.
 11. SHT P3.0 WATER FILTER SYSTEM SHALL
 COMPLY WITH NSF 42. SECTION 611.1
 PROVIDE MANUF. SPECIFICATION SHEETS. -
 MANUF. SPECIFICATION SHEETS NOT
 SUBMITTED.
 13. SHT P4.0 GAS RISER DIAGRAM: THE
 FOLLOWING INFORMATION IS REQUIRED FOR
 THE GAS PERMIT:
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). - PLEASE INDICATE IF THE PIZZA
 OVEN HAS 454,000 BTU TO EACH SECTION OF
 THE PIZZA OVEN. IF NOT PLEASE INDICATE
 HOW MANY BTU'S TO EACH SECTION OF THE
 PIZZA OVEN.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. - TO
 BE SUBMITTED FOR PLAN REVIEW TO VERIFY
 LISTING OF PRODUCT AND TO VERIFY BTU
 LOAD ON THE SYSTEM.
 E. SUBMIT MANUF. SPECIFICATIONS SHEETS
 FOR REQUIRED 2LB TO 1/2 LB REGULATORS.
 THE MANUF. SHEETS ARE REQUIRED AT THE
 TIME OF THE PLAN REVIEW. PLEASE SUBMIT.
 F. SHOW THE LOCATION OF THE REGULATORS
 ON THE GAS RISER DIAGRAM. SECTION
 104.2.1. - IF THE SECONDARY REGULATOR IS
 TO BE INSTALLED ON THE DROP TO THE PIZZA
 OVEN, A SHUT OFF VALVE IS REQUIRED
 UPSTREAM OF THE REGULATOR. IF THIS
 REGULATOR IS INSTALLED, THE THREE
 REGULATORS AT THE PIZZA OVEN WILL NOT BE
 REQUIRED. ONLY THE SHUT OFF VALVES FOR
 THE APPLIANCES WILL BE REQUIRED AT THE
 PIZZA OVENS. IF USING THE THREE
 REGULATORS AT THE OVENS, THE REGULATOR
 ON THE DROP WILL NOT BE REQUIRED. PLEASE
 CLARIFY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved