2006-02-07 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061381
 ADD: 31150 45TH ST
 CONT:FRANCHISE PROPERTIES SERVICES
 INC
 TEL: (316)304-8749
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 1) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 2) COMMENT 3A)FROM THE PREVIOUS REVIEW,
 PLANS DO NOT INDICATE WHICH ARE NEW
 OPENINGS & WHICH ARE EXISTING, PROVIDE
 ADDITIONAL INFORMATION FOR WINDOWS AND
 DOORS.
 ARCHITECTURAL ELEVATIONS INDICATE
 WINDOWS AND MULLION TO REMAIN BUT THE
 STRUCTURAL PLANS S0.1 WIND LOAD NOTES
 WINDOWS, DOORS AND MECHANICAL LOUVERS
 TO WITHSTAND WIND LOADS AND LARGE MISSLE
 IMPACT TESTING.S1 SHOWS DETAIL 9 ON S3.1
  
 NEWLY FRAMED WALL WITH STEEL COLUMNS.
 THE NEWLY FRAMED WALLS DO NOT SHOW ANY
 STRAPPING HOLDING TO THE STEEL COLUMN/
 EXPLAIN HOW STRUCTURAL STATEMENT OF
 WINDOWS, DOORS & LOUVER TO MEET THE WIND
 LOADS & IMPACT STANDARD WITH THE OLD
 GLAZING UNITS?
 1606.2.4 MAIN WIND FORCE RESISTING
 SYSTEM (MWFRS). ALL ELEMENTS AND
 CONNECTIONS OF THE MWFRS SHALL BE
 DESIGNED FOR VERTICAL AND HORIZONTAL
 LOADS BASED ON THE COMBINED LEEWARD AND
 WINDWARD WALL PRESSURES AND ROOF
 PRESSURES DETERMINED FROM TABLE 1606.2A.
 PRESSURES SHALL BE APPLIED IN
 ACCORDANCE WITH THE LOADING DIAGRAMS
 SHOWN IN FIGURE 1606.2A TO THE END
 ZONE AND INTERIOR ZONE AS SHOWN IN
 FIGURE 1606.2B.THE BUILDING SHALL
 BE DESIGNED FOR ALL WIND DIRECTIONS.
 FOR BUILDINGS HAVING FLAT ROOFS, A
 RIDGE LINE NORMAL TO THE WIND DIRECTION
 SHALL BE ASSUMED AT THE MID-LENGTH
 DIMENSION OF THE ROOF FOR ALL DIRECTIONS
 CONSIDERED.EACH CORNER SHALLBE
 CONSIDERED IN TURN AS THE WINDWARD
 CORNER.
 1606.1.4(1) IN WIND BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES
 POSITIVE PRESSURE IN BUILDINGS SHALL BE
 ASSUMED TO BE OPENINGS UNLESS SUCH
 GLAZING IS IMPACT RESISTANT OR PROTECTED
 WITH AN IMPACT RESISTANT COVERING MEET-
 ING THE REQUIREMENTS OF SSTD 12, ASTM
 E 1886 AND ASTM E 1996 OR MIAMI-DADE.
 GLAZED OPENINGS LOCATED WITHIN 30 FT OF
 GRADE SHALL MEET THE REQUIREMENTS OF
 LARGE MISSLE TEST.
  
  
  
 2) COMMENT3B) FROM THE PREVIOUS REVIEW
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 3)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) DOORS
 C)SIDING EFIS
 D) LOUVERS
 E) ROOFING ASSEMBLIES
  
 4) PLANS INDICATE REWORK OF ROOF AND NEW
 PARAPET AND FLASHING, PROVIDE PRODUCT
 TESTING REPORTS FOR ROOFING ASSEMBLIES.
  
 5) PLANS DO NOT PROVIDE WHAT MINIMUM
 TYPE BUILDING DESIGN THIS PLAN WAS
 DESIGNED TO? 601.2.1, 601.2.2.
  
 6) PROVIDE A SITE PLAN WITH DIMENSIONS
 TO THE PROPERTY LINE, TABLE 600 THERE
 MAY BE OPENING ISSUES.
 TODAY I WAS IN A MEETING WITH THE
 CONTRACTOR WHO IS GOING TO BRING IN A
 SURVEY SO TABLE 600 ISSUES MAY BE
 ADDRESSED.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  