Text |
| 2005-07-16 00:00:00 | DENIED |
| | REFERENCE: FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | |
| | |
| | |
| | 1. ALL ARCHITECTURAL SHEETS REQUIRE A |
| | RAISED SEAL AND "WET SIGNATURE". ALL |
| | SHEETS APPEAR TO BE PHOTO COPIES OF |
| | SIGNED, SEALED PLANS. FAC 61G1-61.003 & |
| | FS 481.2055. |
| | 2. ALL SHEETS SIGNED, SEALED, & DATED BY |
| | THE ARCHITECT SHALL CONTAIN A TITLE |
| | BLOCK WITH ALL INFORMATION REQUIRED BY |
| | FAC 61G1-16.004. |
| | 3. ALL MEP SHEETS REQUIRE A RAISED SEAL, |
| | AND A "WET SIGNATURE". ALL MEP SHEET |
| | APPEAR TO BE PHOTO COPIES OF SIGNED, |
| | SEALED PLANS. FAC 61G15-23.002(1)(2) AND |
| | FS 471.025. |
| | 4. SHTS A1.2, A1.3, & A1.4 REFERENCE |
| | EQUIPMENT LAYOUT PLAN, AND EQUIPMENT |
| | SCHEDULES. IF THE EQUIPMENT IN THE |
| | RESTURANT IS BEING ALTERED, MOVED, |
| | ADDED, OR DELETED, PLANS SHALL BE ROUTED |
| | TO DBPR DIVISION OF HOTELS & RESTURANTS |
| | FOR REVIEW. PLANS WILL BE STAMPED BY |
| | DBPR REVIEWERS AND 2 PAGE "WORKSHEETS" |
| | WILL BE ATTACHED TO EACH SET OF PLANS |
| | RESUBMITTED TO CITY OF WPB FOR REVIEW. |
| | SECTION 101.4.7 - PLEASE INDICATE IF THE |
| | FOOD PREP/KITCHEN AREA WILL BE CHANGED |
| | OR IF ALL EQUIPMENT WILL BE REINSTALLED |
| | IN THE SAME LOCATION. SECTION 104.2.1. |
| | 5. SHT A8.3 RESTROOM ELEVATIONS. SHOW |
| | THE FOLLOWING: |
| | (FOR THE URINAL) |
| | B. 11-4.18.2 HEIGHT |
| | C. 11-4.18.3 CLEAR FLOOR SPACE |
| | D. 11-4.18.4 FLUSH CONTROLS |
| | (FOR THE LAVS) |
| | E. 11-4.19.3 CLEAR FLOOR SPACE - LAV IN |
| | MEN'S TOILET ROOM SHALL BE ACCESSIBLE |
| | ALSO FOR USE BY PERSONS USING ACCESSIBLE |
| | URINAL. |
| | F. 11-4.19.5 FAUCETS |
| | 6. SHT A1.2 TURNING AREA REQUIRED IN |
| | SECTION 11-4.22.3 SHALL BE IN THE TOILET |
| | ROOM, NOT THE STALL. |
| | 7. SHT P1.1 ALL FLOOR DRAINS AND KITCHEN |
| | EQUIPMENT SHALL CONNECT TO THE GREASE |
| | SYSTEM. |
| | 8. SHT P1.1 THE DISHWASHER SHALL CONNECT |
| | TO THE SANITARY SYSTEM. UTILTIY |
| | REQUIREMENT. |
| | 9. SHT P1.1 NEW GREASE INTECEPTORS ARE |
| | INDICATED. PLEASE CONTACT LYNN MASSON |
| | ENVIRONMENTAL COMPLIANCE FOR SIZING. |
| | PLEASE CONTACT HER AT (561) 822-2271, |
| | FAX (561) 822-2279, OR E-MAIL |
| | [email protected]. SUBMIT DETERMINATION |
| | SHEET WITH EACH SET OF PLANS WHEN |
| | RESUBMITTING. WASTE ORD. #3434. |
| | 10. SHT P1.1 SHOWS THE CONDENSATE FROM |
| | THE A/C UNITS DRAINING INTO THE |
| | SANITARY. THIS IS NOT APPROVED PER CITY |
| | CODE SECTION 90-125(5). CONDENSATE SHALL |
| | DRAIN SEPARATELY FROM THE BUILDING AND |
| | CONNECT INTO THE STORM LINE, CATCH |
| | BASIN, DRYWELL, OR PLANTED AREA MINIMUM |
| | 1 FOOT FROM THE STRUCTURAL SIDE WALLS. |
| | 11. SHT P3.0 WATER FILTER SYSTEM SHALL |
| | COMPLY WITH NSF 42. SECTION 611.1 |
| | PROVIDE MANUF. SPECIFICATION SHEETS. |
| | 12. SHT P4.0 SANT. & GREASE RISER |
| | DIAGRAMS. SEE COMMENTS 7 AND 8. RISER |
| | DIAGRAMS SHALL REFLECT CHANGES REQUIRED |
| | BY THESE COMMENTS. SECTION 104.2.1. |
| | 13. SHT P4.0 GAS RISER DIAGRAM: THE |
| | FOLLOWING INFORMATION IS REQUIRED FOR |
| | THE GAS PERMIT: |
| | A. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | B. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2 |
| | E. SUBMIT MANUF. SPECIFICATIONS SHEETS |
| | FOR REQUIRED 2LB TO 1/2 LB REGULATORS. |
| | F. SHOW THE LOCATION OF THE REGULATORS |
| | ON THE GAS RISER DIAGRAM. SECTION |
| | 104.2.1. |
| | 14. SUBMIT A WATER RISER DIAGRAM SHOWING |
| | ALL PIPE SIZES, VALVES, WATER HAMMER |
| | ARRESTORS, (REQD BY SECTION 604.9 AND |
| | LOCATED NEAR THE FIXTURE IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING PER |
| | PDI-WH 201). ECT. SECTION 104.3.1.1. |
| | |
| | REVIEW BY KEN STEVENS |