2005-07-21 00:00:00DENIED:
 PLEASE NOTE, ADDITIONAL PERMITS REQUIRED
 FOR HOOD, FIRE SUPPRESSION & WALK-IN
 COOLERS.PLEASE PROVIDE PLANS AND
 MANUFACTURERS SUBMITTAL DATA WITH PERMIT
 APPLICATION.
  
 1.PLANS MUST BE SIGNED, SEALED & DATED
 BY THE ARCHITECT & ENGINEER IN
 ACCORDANCE WITH FS 471.025 & 481.221.
 STAMPS ARE NOT ACCEPTABLE.PRINTED
 NAME, ADDRESS & LICENSE # OR TITLE BLOCK
 IS ALSO REQUIRED PER FAC 61G1-16.004 &
 61G15-23.002 (2).
  
 2.PLEASE CLARIFY WALL TYPES INDICATED
 ON PLAN SHEET A1.1.IT APPEARS ALL
 INTERIOR WALLS ARE "FIRE RATED".PLEASE
 CLARIFY, DOES THIS "RATING" END AT THE
 CEILING?DUCTS PENETRATING "RATED"
 PARTITIONS ARE REQUIRED TO HAVE FIRE
 DAMPERS AT THE PENETRATION OR COMPLY
 WITH 2001 FBC(M) EXCEPTION 3 ITEMS 1
 THROUGH 4.
  
 3.PLAN SHEET M2.1 DETAIL #5 & 10 DO
 NOT INDICATE THE HEIGHT FOR THE ROOF
 CURBS.PER 2001 FBC 1511.7, CURBS SHALL
 BE A MINIMUM OF 8" ABOVE THE ROOF
 SURFACE.
  
 4.PLAN SHEET M2.1 KITCHEN EXHAUST FAN
 DETAIL #2, THE FAN SHALL BE A HINGED
 UPBLAST TYPE PER NFPA 96.
  
 5.PLEASE PROVIDE OUTSIDE AIR
 CALUCALTIONS PER 2001 FBC(M) TABLE
 403.3.
  