Plan Review Notes
Plan Review Notes For Permit 05061381
Permit Number 05061381
Review Stop G
Sequence Number 1
Notes
Date Text
2006-01-31 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 13. SHT P4.0 GAS RISER DIAGRAM: THE
 FOLLOWING INFORMATION IS REQUIRED FOR
 THE GAS PERMIT:
 B. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). - PLEASE INDICATE IF THE PIZZA
 OVEN HAS 454,000 BTU TO EACH SECTION OF
 THE PIZZA OVEN. IF NOT PLEASE INDICATE
 HOW MANY BTU'S TO EACH SECTION OF THE
 PIZZA OVEN.
 D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. - TO
 BE SUBMITTED FOR PLAN REVIEW TO VERIFY
 LISTING OF PRODUCT AND TO VERIFY BTU
 LOAD ON THE SYSTEM.
 E. SUBMIT MANUF. SPECIFICATIONS SHEETS
 FOR REQUIRED 2LB TO 1/2 LB REGULATORS.
 THE MANUF. SHEETS ARE REQUIRED AT THE
 TIME OF THE PLAN REVIEW. PLEASE SUBMIT.
 F. SHOW THE LOCATION OF THE REGULATORS
 ON THE GAS RISER DIAGRAM. SECTION
 104.2.1. - IF THE SECONDARY REGULATOR IS
 TO BE INSTALLED ON THE DROP TO THE PIZZA
 OVEN, A SHUT OFF VALVE IS REQUIRED
 UPSTREAM OF THE REGULATOR. IF THIS
 REGULATOR IS INSTALLED, THE THREE
 REGULATORS AT THE PIZZA OVEN WILL NOT BE
 REQUIRED. ONLY THE SHUT OFF VALVES FOR
 THE APPLIANCES WILL BE REQUIRED AT THE
 PIZZA OVENS. IF USING THE THREE
 REGULATORS AT THE OVENS, THE REGULATOR
 ON THE DROP WILL NOT BE REQUIRED. PLEASE
 CLARIFY.
  
 COMMENTS FROM PLUMBING REVIEW
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]