| 2006-01-31 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 FUEL GAS |
| | |
| | 13. SHT P4.0 GAS RISER DIAGRAM: THE |
| | FOLLOWING INFORMATION IS REQUIRED FOR |
| | THE GAS PERMIT: |
| | B. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2001 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). - PLEASE INDICATE IF THE PIZZA |
| | OVEN HAS 454,000 BTU TO EACH SECTION OF |
| | THE PIZZA OVEN. IF NOT PLEASE INDICATE |
| | HOW MANY BTU'S TO EACH SECTION OF THE |
| | PIZZA OVEN. |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2001 FUEL GAS CODE SEC 402.2. - TO |
| | BE SUBMITTED FOR PLAN REVIEW TO VERIFY |
| | LISTING OF PRODUCT AND TO VERIFY BTU |
| | LOAD ON THE SYSTEM. |
| | E. SUBMIT MANUF. SPECIFICATIONS SHEETS |
| | FOR REQUIRED 2LB TO 1/2 LB REGULATORS. |
| | THE MANUF. SHEETS ARE REQUIRED AT THE |
| | TIME OF THE PLAN REVIEW. PLEASE SUBMIT. |
| | F. SHOW THE LOCATION OF THE REGULATORS |
| | ON THE GAS RISER DIAGRAM. SECTION |
| | 104.2.1. - IF THE SECONDARY REGULATOR IS |
| | TO BE INSTALLED ON THE DROP TO THE PIZZA |
| | OVEN, A SHUT OFF VALVE IS REQUIRED |
| | UPSTREAM OF THE REGULATOR. IF THIS |
| | REGULATOR IS INSTALLED, THE THREE |
| | REGULATORS AT THE PIZZA OVEN WILL NOT BE |
| | REQUIRED. ONLY THE SHUT OFF VALVES FOR |
| | THE APPLIANCES WILL BE REQUIRED AT THE |
| | PIZZA OVENS. IF USING THE THREE |
| | REGULATORS AT THE OVENS, THE REGULATOR |
| | ON THE DROP WILL NOT BE REQUIRED. PLEASE |
| | CLARIFY. |
| | |
| | COMMENTS FROM PLUMBING REVIEW |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |