| Plan Review Notes For Permit 05061381 |
| Permit Number |
05061381 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-07-11 00:00:00 | 1. DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH | | | NFPA 241. | | | | | | 2. DEBRIS SHALL BE REMOVED FROM THE SITE | | | DAILY. | | | | | | 3. EXITS SHALL REMAIN CLEAR AND | | | UNOBSTRUCTED DURING WORK. | | | | | | 4. NO GASOLINE POWERED EQUIPMENT SHALL | | | BE USED INDOORS TO PREVENT CARBON | | | MONOXIDE ACCUMULATIONS WITHIN IT. | | | | | | 5. BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. A MINIMUM OF AT | | | LEAST 6" HIGH NUMBERS ARE REQUIRED. | | | | | | 7. PLANS APPEAR TO HAVE BEEN COPIED. | | | | | | 8. PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATIONS FOR WALLS AND | | | CEILINGS. | | | | | | 9. PLEASE PROVIDE DETAILS ON PROPOSED | | | FIRE WRAP NOTED IN M1.1. | | | | | | 10.SEPARATE PLANS AND PERMITS REQUIRED | | | FOR ANY HOOD, DUCT, AND SUPPRESSION | | | SYSTEM MODIFICATIONS. | | | | | | 11. OCCUPANT LOAD TO BE DETERMINED BY | | | FIRE RESCUE OFFICIALS. | | | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | | OFFICER | | | 835-2910 | | | |
|