2005-07-06 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE SEE ALL SHEETS IN BOTH
 SET OF PLANS SUBMITTED ARE PHOTOCOPIES
 OF SIGNED AND SEALED DRAWINGS. PLEASE
 ALL PLANS MUST BE ORIGINAL SIGNED, DATED
 AND SEALED WITH RAISED SEAL PER FS
 481.221 AND FS 471.025.
 PLEASE SEE MISSING TITLE BLOCK
 INFORMATION ON "A"- SHEETS ETC AS
 REQUIRED UNDER FAC 61G1-16.004 FS
 481.219.
 THE ABOVE IS REQUIRED FOR ALL SHEETS AND
 FOR ALL TRADES WHEATHER OR NOT COMMENT
 IS MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEE 250.50 : COLD WATER
 PIPE TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM.
  
 3)NOTE: PLEASE SEE 250.6,250.24 AND
 EQUIPMENT GROUNDING CONDUCTOR SHALL NOT
 BE INSTALLED UNTIL AFTER THE FIRST MEANS
 OF DISCONNECT.
  
 4)NOTE: PLEASE SEE FEEDERS INDICATED ON
 SCHEDULE. MENTIONS GRNDS FOR NEUTRAL?
 215.5
  
 5)NOTE: PLEASE SEE 210.8B3 2002 NEC,
 REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT
 RECEPTACLES IN NONDWELLING-TYPE KITCHENS
 TO BE GFCI PROTECTED. THIS REQUIREMENT
 APPLIES TO EACH AND EVERY 15- AND
 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE,
 WHETHER OR NOT THE RECEPTACLE SERVES
 COUNTERTOP APPLIANCES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717