| 2005-09-08 00:00:00 | ******* UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE APPLICATION VALUE |
| | NEEDS TO BE INCREASED FOR ALL LABOR AND |
| | MATERIALS. PLEASE SEE FBC 104.6.5 CITY |
| | WIDE ADMINSTRATIVE CODE. |
| | VALUE TO INCLUDE ALL LABOR AND MATERIALS |
| | EVEN IF OWNER SUPPLIED. |
| | THIS WOULD INCLUDE GENERATOR, ATS ETC. |
| | PLEASE SEE VALUE IS SHOWN AS $900 AND |
| | THE MIN OF UNIT ON SPECS SUBMITTED IS |
| | $3600.00 |
| | |
| | 2)NOTE: PLEASE PROVIDE RISER DIAGRAM |
| | WHICH IS TO SHOW INSTALLATION OF NEW |
| | EQUIPMENT INTO EXSITNG SERVICE. |
| | PLEASE PROVIDE, LOCATIONS OF EXISTING |
| | MAIN(S). |
| | PLEASE PROVIDE LOADS AND ITEMS INTENDED |
| | FOR CONNECTION INTO NEW PANEL. |
| | 220.31,702.5, 215.5 |
| | |
| | 3)NOTE: PLEASE PROVIDE MEANS OF |
| | DSICONNECT GROUPED WITH EXISTING MAINS |
| | AS REQUIRED UDNER 225.31, 225.34. PLEASE |
| | BE SURE DISCONNECTING MEANS IS RATED AS |
| | "SERVICE EQUIPMENT". 225.36 |
| | |
| | 4)NOTE: PLEASE INDICATE ON SITE PLAN THE |
| | LOCATION AND DIMENSIONS FROM HOUSEAND |
| | ANY WINDOW/DOOR OR ATTIC OPEINGS. PLEASE |
| | SEE THIS IS A MECHANICAL CODE |
| | REQUIREMENT OF A MIN OF 10' FROM THE |
| | ABOVE LISTED OPENINGS TO A DWELLING |
| | UNIT. |
| | |
| | 5)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | FOR TIE DOWN OF UNIT. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |