Plan Review Notes
Plan Review Notes For Permit 05061379
Permit Number 05061379
Review Stop E
Sequence Number 3
Notes
Date Text
2005-09-08 00:00:00******* UNSAT **********
  
 1)NOTE: PLEASE SEE APPLICATION VALUE
 NEEDS TO BE INCREASED FOR ALL LABOR AND
 MATERIALS. PLEASE SEE FBC 104.6.5 CITY
 WIDE ADMINSTRATIVE CODE.
 VALUE TO INCLUDE ALL LABOR AND MATERIALS
 EVEN IF OWNER SUPPLIED.
 THIS WOULD INCLUDE GENERATOR, ATS ETC.
 PLEASE SEE VALUE IS SHOWN AS $900 AND
 THE MIN OF UNIT ON SPECS SUBMITTED IS
 $3600.00
  
 2)NOTE: PLEASE PROVIDE RISER DIAGRAM
 WHICH IS TO SHOW INSTALLATION OF NEW
 EQUIPMENT INTO EXSITNG SERVICE.
 PLEASE PROVIDE, LOCATIONS OF EXISTING
 MAIN(S).
 PLEASE PROVIDE LOADS AND ITEMS INTENDED
 FOR CONNECTION INTO NEW PANEL.
 220.31,702.5, 215.5
  
 3)NOTE: PLEASE PROVIDE MEANS OF
 DSICONNECT GROUPED WITH EXISTING MAINS
 AS REQUIRED UDNER 225.31, 225.34. PLEASE
 BE SURE DISCONNECTING MEANS IS RATED AS
 "SERVICE EQUIPMENT". 225.36
  
 4)NOTE: PLEASE INDICATE ON SITE PLAN THE
 LOCATION AND DIMENSIONS FROM HOUSEAND
 ANY WINDOW/DOOR OR ATTIC OPEINGS. PLEASE
 SEE THIS IS A MECHANICAL CODE
 REQUIREMENT OF A MIN OF 10' FROM THE
 ABOVE LISTED OPENINGS TO A DWELLING
 UNIT.
  
 5)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FOR TIE DOWN OF UNIT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  