| 2006-12-05 15:37:34 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE KNOW WHEN SUBMITTING REVISIONS ON PLANS |
| | WHICH WERE ORIGINALLY DONE UNDER A BUILDING PERMIT |
| | NUMBER; PLEASE BE SURE WHEN SUBMITTING THE REVISIONS TO |
| | INDICATE # 05061374 |
| | |
| | 2) NOTE: PLEASE 250.50, THE GROUNDING ELECTRODE |
| | ATTACHMENT SHOULD BE MORE THAN THE CWP, AS THIS |
| | BUILDING WOULD HAVE OTHER REQUIRED ATTACHMENT POINTS. |
| | PLEASE KNOW IF THE CWP AT THE LOCATION OF THE |
| | TRANSFORMER CONTAIN CPVC ANYWHERE IN THE SYSTEM BEFORE |
| | IT ACTUALLY ORIGINATES, THEN THE ATTACHMENT WOULD NOT |
| | PROVIDE A SUFFICIENT RESISTANCE OR BE PART OF THE |
| | BUILDING?S SYSTEM. |
| | |
| | 3) NOTE: PLEASE SEE PANEL KPR SEEMS TO INDICATE THE |
| | TRANSFORMER KVA SIZE AS 15K, WHERE AS THE RISER SHOWS |
| | 50. |
| | PLEASE KNOW THIS PART CAN NOT BE REVIEWED FOR THE |
| | CORRECT OCP ETC WITH OUT FIRST KNOWING WHICH SIZE IS |
| | ACCURATE. |
| | PLEASE SEE THE LOAD IS BEING SHOWN HIGHER THAN THAT OF |
| | A 15KVA UNIT. |
| | 240.21, 450.3, 310.16, 240.4, ETC. |
| | |
| | 4) NOTE: PLEASE KNOW, BASED ON THE COMMENT #3, THE |
| | LOADS BACK TO PANEL PP1 HAVE NOT BEEN IDENTIFIED BASED |
| | ON THE OCP AND FEED TO THE EXISTING PANEL KPR. |
| | 220 |
| | |
| | 5) NOTE: PLEASE KNOW WHEN PLANS ARE NOT DONE BY AN |
| | ARCHITECT OR ENGINEER AND DONE BY THE CONTRACTOR, THE |
| | PERSON TAKING RESPONSIBILITY OF THE PLANS SHALL CLEARLY |
| | PRINT AND SIGN THEIR NAME. |
| | FBC106.1.2 ADMIN SECTION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |