Plan Review Notes
Plan Review Notes For Permit 05061374
Permit Number 05061374
Review Stop E
Sequence Number 4
Notes
Date Text
2006-12-05 15:37:34*** UNSAT ***
  
 1) NOTE: PLEASE KNOW WHEN SUBMITTING REVISIONS ON PLANS
 WHICH WERE ORIGINALLY DONE UNDER A BUILDING PERMIT
 NUMBER; PLEASE BE SURE WHEN SUBMITTING THE REVISIONS TO
 INDICATE # 05061374
  
 2) NOTE: PLEASE 250.50, THE GROUNDING ELECTRODE
 ATTACHMENT SHOULD BE MORE THAN THE CWP, AS THIS
 BUILDING WOULD HAVE OTHER REQUIRED ATTACHMENT POINTS.
 PLEASE KNOW IF THE CWP AT THE LOCATION OF THE
 TRANSFORMER CONTAIN CPVC ANYWHERE IN THE SYSTEM BEFORE
 IT ACTUALLY ORIGINATES, THEN THE ATTACHMENT WOULD NOT
 PROVIDE A SUFFICIENT RESISTANCE OR BE PART OF THE
 BUILDING?S SYSTEM.
  
 3) NOTE: PLEASE SEE PANEL KPR SEEMS TO INDICATE THE
 TRANSFORMER KVA SIZE AS 15K, WHERE AS THE RISER SHOWS
 50.
 PLEASE KNOW THIS PART CAN NOT BE REVIEWED FOR THE
 CORRECT OCP ETC WITH OUT FIRST KNOWING WHICH SIZE IS
 ACCURATE.
 PLEASE SEE THE LOAD IS BEING SHOWN HIGHER THAN THAT OF
 A 15KVA UNIT.
 240.21, 450.3, 310.16, 240.4, ETC.
  
 4) NOTE: PLEASE KNOW, BASED ON THE COMMENT #3, THE
 LOADS BACK TO PANEL PP1 HAVE NOT BEEN IDENTIFIED BASED
 ON THE OCP AND FEED TO THE EXISTING PANEL KPR.
 220
  
 5) NOTE: PLEASE KNOW WHEN PLANS ARE NOT DONE BY AN
 ARCHITECT OR ENGINEER AND DONE BY THE CONTRACTOR, THE
 PERSON TAKING RESPONSIBILITY OF THE PLANS SHALL CLEARLY
 PRINT AND SIGN THEIR NAME.
 FBC106.1.2 ADMIN SECTION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717